System Options
Dial Tone Detection Disabled
10. Select Y (do disable) or N (do not disable) by pressing the up or down arrow key, then press ENTER.
Monitor Line
Enable the line monitor for each phone line that will be used. See Figure 8.8 for the location of this field on the phone lines screen. When the
phone line monitor has been enabled for a phone line, a trouble condition will occur if the line is not connected. If a phone line will not be
used, it must be disabled.
11. Select Y (monitor line) or N (do not monitor line) by pressing the up or down arrow key, then press ENTER.
Answering Machine Bypass
This option is used in conjunction with the HFSS Honeywell Fire Software Suite. This feature ensures that an answering machine will not
interfere with communication between the panel and the computer. If an answering machine is used at the panel site, enable this feature; if an
answering machine is not used, disable the feature.
This option is factory-programmed as Yes (enabled).
The selection made here must match the programming for this option in the Communication Configuration dialog box of HFSS.
Select Y (answering machine bypass enabled) or N (answering machine bypass disabled) by pressing the up or down arrow, then press
ENTER.
Phone Line Unused
This option is used so that you can set unused phones lines to "Yes", so no auto-test will be sent through that line.
This option is factory programmed as No.
12. Select Y or N by pressing the up or down arrow key, then press ENTER.
Edit Ethernet
1.
Login to the panel. The panel will automatically access the main menu.
2.
Select 7 to access Panel Programming.
3.
Select 5 to access System Options.
4.
From the next menu, select 1 to access Communication Options.
5.
Select 3 to access Edit Ethernet.
AlarmNet Timers
1.
Login to the panel. The panel will automatically access the main menu.
2.
Select 7 to access Panel Programming.
3.
Select 5 to access System Options.
4.
From the next menu, select 1 to access Communication Options.
5.
Select 4 to access the AlarmNet Timers.
6.
The available options for AlarmNet Timers are as follows:
• Ethernet: 5 minutes (default), 3 minutes, 90 seconds, 75 seconds, none, 30 days, 24 hours, 1 hour.
• Cellular: 24 hours (default), none, 30 days
• Old Alarm: 30 minutes (default), 15 minutes, 10 minutes, none, 24 hours,12 hours, 6 hours, 4 hours,2 hours, 1 hour
Phone Line Gains
1.
Login to the panel. The panel will automatically access the main menu.
2.
Select 7 to access Panel Programming.
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
E
European format. Uses the 66 msec / 34 msec make/break ratio.
MAC:0000.0020.6894
MAC CRC:01E2
IP:158.100.049.148
<IP Address> More
Figure 8.9 Edit Ethernet Message
Ethernet: 5 Minutes_
Cellular: 24 Hours_
Old Alarm: 30 Minutes_
<Ethernet Supervise>
Figure 8.10 AlarmNet Timers
Sub:255.255.252.000
GW:158.100.048.254
DHCP:Y
<DHCP enable>