Group; 1: Edit Group; 2: View Group Points; 3: Edit Output Group Template - Honeywell SILENT KNIGHT 6700 Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Programming
5.
Enter the number of the zone you want to view, then press ENTER.

8.4 Group

An output group is made up of output points that have been programmed to respond in the same way. output groups simplify programming,
because you do not have to program each individual point. Once you have defined the characteristics of output groups, you can assign each
point to the appropriate group. Up to 125 output groups can be defined.
8.4.1 Edit Group
In the Edit Group option, you can program the name of an output group and change the properties of that group. To edit a group, follow these
steps:
1.
Login to the panel.
2.
Select 7 to access the Program Menu.
3.
Press 3 to enter the Group Menu.
4.
Press 1 to edit the group.
5.
Enter the number of the group you want to edit, then press ENTER.
Edit Group Name
6.
To edit the group name, press 1.
You can use words to display a descriptive name for a group.
NOTE: See Appendix A for information to edit names.
Edit Group Properties
7.
To edit the group properties, press 2 from the Edit Group menu.
The Edit Group menu allows you to select the options for each group for the following items:
Template Override: Y or N
If you select Yes to access Template Override, the Template Override Cadence is available.
See Section 8.4.3 for more information.
8.4.2 View Group Points
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 7 to access the Panel Programming.
3.
Press 3 to enter the Group Menu.
4.
Press 2 to view the Group Points.
5.
Enter the group number, then press ENTER..
8.4.3 Edit Output Group Template
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 7 to access the Panel Programming.
78
GROUP: G01
POINT: 01:001
NUMBER: 1 of 12
Figure 8.3 View Zone Points Screen
Group 001 Properties
Voice Group: N
Select Switch:00
More
Figure 8.4 Group Properties Screen Programming Options
Group: G91 of 8
Point: 98:001
Number: 1 of 8
Figure 8.5 View Group Points
zone number
Allow Sys Override: N
Template Override: Y
Template Override
Cadence: 23
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Group

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents