6860 Remote Annunciator Installation

4.9 6860 Remote Annunciator Installation
The optional 6860 Remote Annunciator can be surface or flush mounted.
6860 installation involves the following steps:
1.
Ensure power is off at the panel.
2.
Mount the 6860 in the desired location (see Section 4.9.1).
3.
Connect the 6860 to the panel (see Section 4.9.2).
4.
Use the DIP switches on the back of the 6860 to assign an SBUS ID# (see Section 4.13.1).
5.
The 6860 module must be added to the system through programming. JumpStart Auto-Programming will add the module automatically
(see Section 8.2).
4.9.1 Mounting the 6860
This section of the manual describes mounting the remote annunciator. The annunciator can be flush or surface mounted.
Flush Mounting
This section of the manual describes flush mounting. Follow these steps to flush mount the 6860.
1.
The back box dimensions are 9-1/4" W x 8-3/8" H. The minimum depth required is 2". The backbox can be mounted prior to the
complete installation of the RA-2000FIK-RA2000TR-RD2G/R6860 using any of the mounting holes shown below.
2.
Remove knockouts as needed for wires. There are 10 knockouts available, two on each side and two in the back of the cabinet.
3.
Wire the annunciator board to the main control panel as shown in Figure 4.27.
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
BACK
BACK
BACK
NEXT
NEXT
NEXT
Model 6860
Figure 4.23 6860 Remote Annunciator
mounting holes
mounting holes
Figure 4.24 6860 Backbox Mounting
Control Panel Installation
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents