Programming
Daylight Saving Time Start and End
This option allows you to adjust the week and month Daylight Saving Time (DST) starts and ends. For this feature to work, you must enable
(set to Yes) the Automatic Daylight Savings Adjustment option under Daylight Savings Options. The default values for the DST Start and
End are:
DST Start: The second Sunday in March
DST End: The first Sunday in November
To set the start and end for Daylight Saving Time, refer the following steps:
1.
Press the up or down arrow key to select the week (1st, 2nd, etc.) Daylight Saving Time starts.
Then, press ENTER to make your selection and move the cursor to the month setting.
2.
Press the up or down arrow key to select the month (January – December) Daylight Saving Time starts.
Then, press ENTER to make your selection and move the cursor to the DST End option.
3.
Press the up or down arrow key to select the week (1st, 2nd, etc.) Daylight Saving Time ends.
Then, press ENTER to make your selection and move the cursor to the month setting.
4.
Press the up or down arrow key to select the month (January – December) Daylight Saving Time ends.
Then, press ENTER two times to make your selection and exit.
8.6.5 Edit Banner
The banner is the message that displays on the panel LCD when the system is normal. For example, a system is normal when no alarms or
troubles exist and no one is currently using the system menus. You can create a custom message, which can be up to 40 characters, two lines
of 20 characters each. If you do not create a custom message, the system will use the internal banner. You cannot change the internal banner.
To customize the banner display message, do the following.
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 7 for Edit Banner.
NOTE: See Appendix A for instructions on how to edit the banner.
5.
To select each character of a word, press the up or down arrow. Then, press the right arrow key to move to the next character.
6.
After you enter the word or the sentence, press ENTER to move the cursor to line two of the custom banner.
8.6.6 SLC Family
The 6700 supports SD or SK Series SLC devices. You must configure the 6700 to accept the protocol of the devices you are installing. You
cannot mix SLC devices of different protocols.
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 8 for SLC Family.
5.
Press UP arrow to select the desired SLC device type.
6.
Press ENTER to accept the displayed SLC device type.
NOTE: When you change the SLC type from one protocol to another, the following message will appear.

8.7 JumpStart Auto-Programming

The FACP supports an incremental JumpStart. For example, after the initial JumpStart and customization, if you add more devices and per-
form JumpStart again, the additional devices are added. You will not lose any of your previous custom programming.
To run JumpStart auto-programming:
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 6 to access JumpStart Auto-Programming.
4.
From the Warning screen, press the up or down arrow to select "Yes".
5.
Press ENTER.
88
Changing the SLC
family will set all
SLC points to
[Press for More]
Figure 8.14 SLC Family Change
family will set all
SLC points to
UNUSED
Back
Accept