Honeywell SILENT KNIGHT 6700 Manual page 64

Addressable fire alarm control panel
Table of Contents

Advertisement

Programming Overview
System
Emergency
Advisory
1
Temporal 4 coding cannot not be used for NAC circuits on CO Supervisory events.
Figure 7.4 Example of Zone Events Mapped to Output Groups and Patterns
Zone 3
Offices
3rd floor
Zone 2
Storage
2nd floor
Zone 1
Show Room
1st floor
same floor
floor above
floor below
64
Zone
Trouble
Status Point Active
Zone 1:
manual pull alarm
This example shows Zone 1 manual pull alarm event mapped to:
• Group 1 using constant output.
• Group 5 using ANSI 3.41 output pattern.
ANSI 3.41
manual pull
ANSI 3.41
detector alarm
constant
supervisory
Figure 7.5 Example of Zone Events Mapped to Output Groups and Patterns
SBUS Expander Trouble
SBUS Class A Trouble
SLC Loop Trouble
AC Loss Trouble
Battery Trouble
Ground Fault Trouble
Phone Line Trouble
Reporting Account Trouble
Table 7.2 Event Types
pattern 00
constant
pattern 02
ANSI 3.41
Group 3
3rd floor
notification
Group 2
2nd floor
notification
Group 1
Show Room
1st floor
notification
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Panel
General Trouble
Site Silenced
F1 Key Active
F2 Key Active
F3 Key Active
F4 Key Active
group 1
group 2
group 3
group 4
group 5
group 6
through
group 125
Zone 3
Offices
3rd floor
ANSI 3.41
Zone 2
manual pull
Storage
ANSI 3.41
2nd floor
detector alarm
constant
supervisory
Zone 1
1st floor
Mapping Overview
Site
Group 3
3rd floor
notification
Group 2
2nd floor
notification
Group 1
1st floor
notification

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents