Programming
3.
Select 5 to access System Options.
4.
From the next menu, select 1 to access Communication Options.
5.
Select 5 to access Phone Line Gains.
6.
The available options are listed as follows:
• Dialing: Low, High (default), Normal
• Reporting: Low (default), High, Normal
8.6.2 Time Options
Use this programming option to set the following:
water flow delay time
low AC report delay
clock format
enable or disable automatic daylight savings time adjustment
AC clock frequency
Waterflow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a waterflow switch. The delay is system-
wide. All waterflow switches on the system will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 4 to access Time Options.
A screen similar to the one shown below will display.
Water Flow Delay:01s
Alarm Verify:060s
AC Report Delay:03h
<(0-90)>
5.
Enter the number of seconds (0 to 90) to delay an a waterflow switch alarm, then press ENTER.
Alarm Verify
You can set the alarm verification time from 60 to 250 seconds (default is 60 seconds).
NOTE: For UL installations, the Alarm Verification Time cannot be less than 60 seconds.
To set the alarm verification:
6.
Enter the desired number of seconds for the alarm verification time.
7.
Press the right arrow or press ENTER to make your selection and move the cursor to the next programming option.
AC Report Delay
NOTE: You must select 1-3 hours in UL central station installations and UL remote signaling installations.
You can adjust the number of hours before a low AC report will be sent to the central station.
86
Dialing: High
Reporting: Low
<Dialing Gain>
Figure 8.11 Phone Line Gains
delay in seconds
before waterflow
alarm occurs (00-90)
More
Figure 8.12 Water Flow Delay Programming Screen
AC-Frequency: 60Hz
Clock Format: AMPM
Auto-Resound: 24hr
<50Hz/60Hz/Internal>
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022