Control Panel Installation
Note: 0.25" spacing must be
maintained between each of these
circuit types; as well as between
power-limited and non-power-limited
circuits.

4.4 AC Power Connection

At installation, connect the AC terminals to the power source as shown in Figure 4.5. It may be necessary for a professional electrician to
make this connection.
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
!
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF
POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR
INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED
AC power for the 6700 is rated at 120VAC, 60Hz, 1.5A.
26
AC input
Phone lines
Battery
connection
Relays
Battery
Figure 4.4 Wire Routing Example
PRI: 120V,
60Hz, BLK-
WHT SEC:
36V, 85VA
YEL-YEL
120V
earth
supervised AC input
ground
Figure 4.5 AC Power Connection
7
Battery
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
AC Power Connection
NAC circuits
SBUS
SLC