4.11.4 Dry Contact Wiring
The eight input circuits on the 5880 board are for monitoring switch inputs. Any type of switch supported by the control panel can be used
with the 5880. For example, you can use a 5880 to monitor pull stations, water flow, tamper, reset, or silence switches.
Wire dry contacts as shown below. Notice grouping of terminals. Power terminals are shared by two inputs.
4.7kΩ EOL
42
P1
Pin #
1
2
3
4
5
6
7
8
9
10
11
12
P2
Pin #
1
2
3
4
5
6
7
8
9
10
11
12
Figure 4.32 5880 Board Layout
resistors
IN - 48
C+
IN - 47 IN - 46
5880
Figure 4.33 Dry Contact Wiring
C+
IN - 45 IN - 44
C+ IN - 43 IN - 42
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
5880 LED Driver Module
Cathode
LEDs
Anode
Cathode
P3 and P4 are wired
LEDs
the same as P2.
Anode
supervised
wiring
C+
IN - 41