3: Miscellaneous Options; 4: Daylight Saving Options - Honeywell SILENT KNIGHT 6700 Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

System Options
To program a low AC report delay, follow these steps:.
8.
Enter the number of hours before a low AC report will be sent to the central station, then press ENTER.
AC Line Frequency
The panel's AC line frequency is selectable for 50 or 60 Hz or Internal. The AC Frequency feature dictates how the control panel will calcu-
late time based on the AC line frequency used in the installation site. The "Internal" option can be used in areas where the AC line frequency
is not dependable and you want the panel to calculate time from the internal crystal. The internal crystal is not as accurate as the AC power
source and internal 60 Hz or 50 Hz should normally be selected. The panel defaults to the 60 Hz selection. To change the AC line frequency,
continue programming from steps above:
9.
Select 50 Hz, 60 Hz or Intl, by pressing the up or down arrow key. Then, press ENTER.
Clock Display Format (AM/PM or Military)
To change the system clock display format, continue programming from step 8 above:
10. Select AMPM (for AM/PM display format) or MIL (for military or 24 hr display format) by pressing the up or down arrow, then press
ENTER.
Auto-Resound (4 or 24 hours)
The system resound time period can be modified from the default value 24 hours to 4 hours. This setting adjusts when the FACP will auto-
matically resound events after being silenced. Set this option to 4 hours when using SWIFT devices.
8.6.3 Miscellaneous Options
Through this programming option, you can turn on or off strobe synchronization during silence, display status at Idle (auto display event),
report by zone or point, and single key acknowledge.
To edit miscellaneous options:
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 5 to access Miscellaneous Options.
Strobes Active when Silenced
When "SYNC Strobe" is selected as Y (Yes), the strobes will continue to flash when the system is silenced and will stop flashing when the
system is reset.
NOTE: "SYNC Strobe" only functions with outputs that use a synchronized output pattern.
5.
Press the up or down arrow key to toggle this selection between Y (Yes) or N (No).
6.
Press right arrow key or ENTER to make your selection and move to the next programming option.
Auto Display Events
When this feature is programmed Y (Yes), the highest priority event of the system in control will automatically display on the control panel
and remote annunciators after there has been no activity on any system touch pad for two minutes.
7.
Press the up or down arrow key to toggle this selection between Y (Yes) or N (No).
8.
Press right arrow key or ENTER to make your selection and move to the next programming option.
8.6.4 Daylight Saving Options
To edit daylight savings:
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 6 for Daylight Savings.
Automatic Daylight Saving Adjustment
The control panel has an automatic DST (Daylight Saving Time) adjustment feature. If this feature is not enabled (set to No), the Daylight
Saving Time change is not made to the system clock.
To enable or disable DST adjustment, continue programming:
5.
Select Y (enabled) or N (disabled) by pressing the up or down arrow, then press ENTER.
6700 Manual — P/N LS10148-001SK-E:F 8/29/2022
Water Flow Delay:01s
Alarm Verify:060s
AC Report Delay:03h
<Low AC(0-30h)> More
Figure 8.13 Low AC Report Delay Programming Screen
low AC report delay
in hours (00-30)
Programming
87