GENERATOR START-UP PROCEDURE (AUTO MODE)

STARTING (AUTO MODE)
DANGER
Before connecting this generator to any
building's electrical system, a licensed
electrician must install an isolation
(transfer) switch. Serious damage to
the building's electrical system may occur
without this transfer switch.
NOTICE
When connecting the generator to an isolation (transfer)
switch, ALWAYS have power applied to the generator's
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
NOTICE
When the generator is set to AUTO mode, the generator
will automatically start in the event of commercial
power falling below a prescribed level by means of a
contact closure that is generated automatically by a
transfer switch.
WARNING
When operating the generator in AUTO mode,
remember that the generator can start up at any
time without warning. NEVER attempt to perform any
maintenance while the generator is in Auto mode.
CAUTION
The engine speed switch must be set to the High
position when running in Auto mode. Failing to set
the switch in the proper position can result in damage
to the generator when it turns on.
NOTICE
When the Auto Start/Stop switch is placed in the
AUTO position, the engine glow plugs will be warmed
and the engine will start automatically.
PAGE 36 — DCA25SSIU4FC8 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (08/23/22)
1. Perform steps 1–6 under Before Starting in the
Generator Start-Up Procedure (Manual) section.
2. Place the Engine Speed switch in the HIGH position
(Figure 56).
Figure 56. Engine Speed Switch (High Position)
3. Place the Auto Start/Stop switch (Figure 57) in the
AUTO position.
AUTO
OFF/RESET
Figure 57. Auto Start/Stop Switch
(Auto Position)
4. Once the start signal is received (the remote-start
contacts are closed), the pre-heating process will begin.
When the pre-heating process has completed, the
engine will start automatically and accelerate to rated
speed. When the remote-start contacts are opened,
the engine will stop.
5. If the engine fails to start, perform the manual starting
procedure.