Connecting Loads
Loads can be connected to the generator by the output
terminal lugs, convenience receptacles, or optional
cam-loks (Figure 10). Make sure to read the operation
manual before attempting to connect a load to the generator.
To protect the output terminals from overload, a 3-pole,
60-amp, main circuit breaker is provided. Make sure to
switch ALL circuit breakers to the OFF position prior to
starting the engine.
HARD WIRE
HOOKUP PANEL
U
V
O
W
GROUND
LOAD
NEUTRAL
CAMLOCKS
Figure 10. Connecting Loads
PAGE 22 — DCA25SSIU4FC8 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (08/23/22)
OUTPUT TERMINAL PANEL FAMILIARIZATION
CS-6369
TWIST-LOCK
RECEPTACLES
LOAD
GFCI
RECEPTACLE
LOAD
Overcurrent Relay
An overcurrent relay (Figure 11) is connected to the
main circuit breaker. In the event of an overload, both the
circuit breaker and the overcurrent relay may trip. If the
circuit breaker can not be reset, the Reset button on the
overcurrent relay must be pressed. The overcurrent relay
is located inside the control box.
Figure 11. Overcurrent Relay
NOTICE
The overcurrent relay monitors the current flowing
from the U,V, and W output terminal lugs to the load.
In the event of a short circuit or overcurrent condition,
it will automatically trip the 60-amp main circuit breaker.
To restore power to the output terminal panel, press
the Reset button on the overcurrent relay and place
the main circuit breaker in the closed (ON) position.
TEST
RESET
MC
MC