Maintenance - MQ Power WHISPERWATT DCA25SSIU4FC8 Operation Manual

Table of Contents

Advertisement

Table 14. Inspection/Maintenance
Check Engine Oil and Coolant Levels
Check Fuel Filter/Water Separator Bowl
Check Air Cleaner
Check Air Cleaner Element
Check for Leaks/Hoses/Clamps
Check for Loosening of Parts
Drain Water in Fuel
Change Engine Oil and Oil Filter *
Clean Unit, Inside and Outside
Replace Fuel Filter Elements
Check Engine Mounts
Service Battery
Check Air Intake Hoses
Check Fan Belt Condition (Replace if Necessary)
Engine
Check Automatic Belt Tensioner
Check Electrical Ground Connection
Clean Radiator, Check Cooling System
Coolant Solution Analysis, Add SCAs as Required
Pressure Test Cooling System
Check Engine Speed
Test Thermostats
Test Glow Plugs
Flush and Refill Cooling System
Clean Inside of Fuel Tank
Replace Air Cleaner Elements *
Check Battery Acid Level
Drain Environmental Tank
Check All Hoses and Clamps
Measure Insulation Resistance Over 3M Ohms
Generator
Check Rotor Rear Support Bearing
*
During initial operation of a new engine, change oil and filter between a minimum of 100 hours and a maximum of 250 hours. Service interval
1
depends on type of oil.
*
2
Add supplemental coolant additives (SCAs) to recharge the engine coolant.
*
Replace the primary air filter element when the restriction indicator shows a vacuum of 625 mm (25 in. H
3
*
If the blowby hose needs to be replaced, ensure that the slope of the blowby hose is at least 1/2 inch per foot, with no sags or dips that could
4
collect moisture and/or oil.
A
*
ccumulation of carbon (soot, unburned fuel) in the exhaust pipeline and muffler could cause not only system derates but also could lead to a fire
5
incident. To destroy the soot and unburned fuel, run the unit at rated power for some period of time until the exhaust gas become mostly colorless
every 250 hours of operation time. The carbon will be generated easier when the unit operates at less then 40% of rated power. In this case,
perform the above procedures at a shorter interval time.
A
*
pplying a large load at one time to the unit when carbon deposits have accumulated in the exhaust system could produce fire/sparks which
6
could lead to abnormal combustion. Therefore it is recommended to appy the load gradually and observe the exhaust gas color (colorless)
during the process.
Fire or sparks may be emitted from the exhaust gas outlet during the carbon emission accumulation check (load). Make sure the area
*
7
surrounding the unit is free from any flammable material.
PAGE 38 — DCA25SSIU4FC8 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (08/23/22)
10 Hours
or Daily
X
X
X
X
X
X
X
1
X
X
3
X
Every
500 Hours
250
or Every
Hours
12 Months
X
X
X
X
X
X
X
X
X
X
X
X
X
X
0).
2

MAINTENANCE

1,000 Hours
or Every
Other
36 Months
3,000 hours
3,000 hours
2,000 hr. or 2 yr.
X
As Required
X