Generator Start-Up Procedure (Auto Mode) - MQ Power DCA300SSJU4F3 Operation Manual

60hz generators
Table of Contents

Advertisement

GENERATOR START-UP PROCEDURE (AUTO MODE)

STARTING (AUTO MODE)
DANGER
Before connecting this generator to any
building's electrical system, a licensed
electrician must install an isolation
(transfer) switch. Serious damage to
the building's electrical system may occur
without this transfer switch.
CAUTION
When connecting the generator to a isolation (transfer)
switch, ALWAYS have power applied to the generator's
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
NOTICE
When the generator is set in the AUTO mode, the
generator will automatically start in the event of
commercial power falling below a prescribed level
by means of a contact closure that is generated
automatically by a transfer switch.
WARNING
When running the generator in the AUTO mode,
remember the generator can start up at any time without
warning. NEVER attempt to perform any maintenance
when the generator is in the auto mode.
NOTICE
When the Auto Off/Reset Manual Switch is placed
in the AUTO position, the engine glow plugs will be
warmed and the engine will start automatically.
DCA300SSJU4F2/F3 60 HZ GENERATOR• OPERATION MANUAL — REV. #2 (04/18/22) — PAGE 47
When starting generator in AUTO mode use the "Manual
Start-up" procedure except where noted (see below).
1. Perform steps 1 through 5 in the Before Starting section
as outlined in the Manual Starting Procedure.
2. Place the Auto Off/Reset Manual Switch (Figure 60)
in the AUTO position.
Figure 60. Auto Off/Reset Manual Switch
3. Continue operating the generator as outlined in the
Manual Start-up procedure (start at step 2).
NOTICE
If the unit has Power Balance™ installed and once
the main breaker is closed, the Power Balance™
should activate after 1 minute if the load is below 30%
of rated load.
If at any time the load spikes to 90% or more, the Power
Balance will immediately drop out and wait 5 minutes
to re-evaluate the load.
(AUTO)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dca300ssju4f2Whisperwatt series