Omron CK3M Seres Hardware User Manual page 215

Programmable multi-axis controller
Table of Contents

Advertisement

Relation between Input Current to the Digital Input and Sensor
Control Output (Load Current)
I
(min) ≤ I
OUT
ON
Precautions for Correct Use
The digital input is constant current type input.
For constant current type input, the input current does not increase linearly with the input volt-
age.
If you gradually raise the input voltage, once the input current reaches I
does not increase and remains roughly constant even when the input voltage is raised.
When I
is smaller than I
ON
be calculated as follows:
R ≤ (V
- V
) / (I
CC
R
Power W of bleeder resistor ≥ (V
V
: Input voltage of digital input
CC
V
: Output residual voltage of sensor
R
I
: Input current of digital input
ON
I
: Sensor control output (load current)
OUT
Relation between OFF Current of the Digital Input and Sensor Leak-
age Current
The digital input cannot detect sensor output OFF unless the following conditions are satisfied:
I
≥ I
OFF
leak
When I
is greater than I
leak
Use the following equation to calculate the bleeder resistance constant.
R ≤ (V
/ I
OFF
OFF
Power W of bleeder resistor ≥ (V
Two-wire sensor
V
R
V
V
: Power supply voltage
CC
CK3M/CK5M Series Programmable Multi-Axis Controller Hardware User's Manual (O036)
≤ I
(max)
OUT
(min), connect a bleeder resistor R. The bleeder resistor constant can
OUT
(min) - I
)
OUT
ON
2
− V
)
CC
R
, connect a bleeder resistor R.
OFF
) × V
/ (I
× (V
/ I
OFF
leak
OFF
2
− V
)
CC
R
Digital input
R
CC
V
: Output residual voltage of sensor
R
/ R × 4 [allowable margin]
) - V
)
OFF
OFF
/ R × 4 [allowable margin]
5 Wiring
, the input current
ON
5-37