Omron CK3M Seres Hardware User Manual page 193

Programmable multi-axis controller
Table of Contents

Advertisement

The applicable ferrules, wires, and crimping tools are listed in the following table.
Manufactur-
er
Phoenix Con-
tact
Weidmüller
 Using Twisted or Solid Wires
Wire type
Solid wire
Twisted wire
Required Tools
Use a flat-blade screwdriver to remove wires.
The recommended screw driver is as follows.
Model
SZF 0-0,4X2,5 Phoenix Contact
Connecting Ferrules
Insert the ferrule straight into the terminal hole.
It is not necessary to press a flat-blade screwdriver into the release hole.
After you make a connection, make sure that the ferrule is securely connected to the terminal block.
Connecting Twisted Wires/Solid Wires
Use the following procedure to connect the twisted wires or solid wires to the terminal block.
1
Press a flat-blade screwdriver straight into the release hole.
If you press in the screwdriver correctly, you will feel the spring in the release hole, and the
screw driver will begin to incline.
CK3M/CK5M Series Programmable Multi-Axis Controller Hardware User's Manual (O036)
Applicable wire
Ferrule model
2
(mm
AI0,25-8
0.25 (#24)
AI0,5-8
0.5 (#20)
AI0,75-8
0.75 (#18)
H0.25/12
0.25 (#24)
H0.34/12
0.34 (#22)
H0.5/14
0.5 (#20)
H0.75/14
0.75 (#18)
Conductor cross-sectional area
2
0.2 to 1.5 mm
Manufacturer
Ferrule
(applicable wire size given in parentheses)
(AWG))
Phoenix Contact
CRIMPFOX 6 (0.25 to 6 mm
Weidmüller
PZ6 Roto (0.14 to 6 mm
Conductor length
(stripping length)
8 mm
5 Wiring
Crimping Tool
2
, AWG24 to 10)
2
, AWG26 to 10)
5
5-15

Advertisement

Table of Contents
loading