Output Terminal Panel Connections - MQ Power DCA300SSJU4F3 Operation Manual

60hz generators
Table of Contents

Advertisement

UVWO TERMINAL OUTPUT VOLTAGES
Various output voltages can be obtained using the UVWO
output terminal lugs. The voltages at the terminals are
dependent on the placement of the jumpers plates (6) on
the Voltage Change-Over Board and the adjustment of
the Voltage Regulator Control Knob.
Remember the voltage change-over board determines the
range of the output voltage and can be configured in two
different positions that provide 6 different output voltages
at the UVWO output terminals. The generator is shipped
from the factory in the 240V configuration. The voltage
regulator (VR) allows the user to increase or decrease the
selected voltage.
3Ø-240V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 240V
operation as shown in Figure 27
X
1
Y
2
Z
3
O
Figure 27. Voltage Change-Over Board 240V
Configuration
2. Connect the load wires to the UVWO terminals as
shown in Figure 28
RED
BLACK
U
V
THREE-PHASE
240 VAC (LOAD CONNECTIONS)
Figure 28. UVWO Terminal Lugs
3Ø-240/1Ø-139 Connections
DCA300SSJU4F2/F3 60 HZ GENERATOR• OPERATION MANUAL — REV. #2 (04/18/22) — PAGE 37

OUTPUT TERMINAL PANEL CONNECTIONS

JUMPER
6 PLACES
U
U
2
1
4
V
V
2
1
5
W
W
2
1
6
BLUE
WHITE
GREEN
W
O
GROUND
CONNECTION
MUST
BE USED
AT ALL TIMES
3. Turn the voltage regulator knob (Figure 29) clockwise
to increase voltage output, turn counterclockwise to
decrease voltage output. Use voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required
Figure 29. Voltage Regulator Knob
1Ø-240V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 27.
2. Connect the load wires to the UVWO terminals as
shown in Figure 30.
RED
BLACK
U
V
240V
240V
SINGLE-PHASE
240 VAC (LOAD CONNECTIONS)
Figure 30. UVWO Terminal Lugs
1Ø-240V Connections
1Ø-120V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 27.
2. Adjust voltage regulator knob (Figure 29) for an output
of 208V to obtain 120V at the UVWO terminals.
3. Connect the load wires to the UVWO terminals as
shown in Figure 31
RED
BLACK
U
V
SINGLE-PHASE
120 VAC (LOAD CONNECTIONS)
Figure 31. UVWO Terminal Lugs 1Ø-120V
Connections
BLUE
GREEN
WHITE
O
W
240V
GROUND
CONNECTION
MUST
BE USED
AT ALL TIMES
BLUE
GREEN
WHITE
O
W
120V
120V
120V
GROUND
CONNECTION
MUST
BE USED
AT ALL TIMES