UVWO TERMINAL OUTPUT VOLTAGES
Various output voltages can be obtained using the UVWO
output terminal lugs. The voltages at the terminals are
dependent on the placement of the jumper plates (6) on
the Voltage Change-Over Board and the adjustment of
the Voltage Regulator Control Knob.
Remember the voltage change-over board determines the
range of the output voltage and can be configured in two
different positions that provide 6 different output voltages
at the UVWO output terminals. The generator is shipped
from the factory in the 240V configuration. The voltage
regulator (VR) allows the user to increase or decrease the
selected voltage.
3Ø-240V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 240V
operation as shown in Figure 27.
X
U
1
Y
V
2
2
Z
W
3
O
Figure 27. Voltage Change-Over Board
240V Configuration
2. Connect the load wires to the UVWO terminals as
shown in Figure 28.
Figure 28. UVWO Terminal Lugs
3Ø-240/1Ø-139 Connections
DCA180SSJU4F/F3 60 HZ GENERATOR• OPERATION MANUAL — REV. #0 (03/25/22) — PAGE 37

OUTPUT TERMINAL PANEL CONNECTIONS

JUMPER
6 PLACES
U
2
1
4
V
1
5
W
2
1
6
3. Turn the voltage regulator knob (Figure 29) clockwise
to increase voltage output, turn counterclockwise to
decrease voltage output. Use the voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required.
DECREASE
Figure 29. Voltage Regulator Knob
1Ø-240V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 27.
2. Connect the load wires to the UVWO terminals as
shown in Figure 30.
Figure 30. UVWO Terminal Lugs
1Ø-240V Connections
1Ø-120V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 27.
2. Adjust the voltage regulator knob (Figure 29) for an
output of 208V to obtain 120V at the UVWO terminals.
3. Connect the load wires to the UVWO terminals as
shown in Figure 31.
Figure 31. UVWO Terminal Lugs
1Ø-120V Connections
INCREASE