UVWO TERMINAL OUTPUT VOLTAGES
Various output voltages can be obtained using the UVWO
output terminal lugs. The voltages at the terminals are
dependent on the placement of the jumper plates (6) on
the voltage change-over board.
The voltage change-over board determines the range of
the output voltage and can be configured in two different
positions that provide 6 different output voltages at the
UVWO output terminals. The generator is shipped from
the factory in the 240-volt configuration.
3-Phase 240-Volt UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 240-volt
operation as shown in Figure 14.
X
U
1
Y
V
2
2
Z
W
3
O
Figure 14. Voltage Change-Over Board
3-Phase 240/139-Volt Configuration
2. Connect the load wires to the UVWO terminals as
shown in Figure 15.
RED
BLACK
U
V
THREE-PHASE
240 VAC (LOAD CONNECTIONS)
Figure 15. UVWO Terminal Lugs
3-Phase 240-Volt Connections
PAGE 26 — DCA180SSJU4F3PD 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (11/01/22)

OUTPUT TERMINAL PANEL CONNECTIONS

JUMPER
6 PLACES
U
2
1
4
V
1
5
W
2
1
6
BLUE
GREEN
WHITE
O
W
GROUND
CONNECTION
MUST
AT ALL TIMES
Single-Phase 240-Volt
UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 240-volt operation as shown in Figure 14.
2. Connect the load wires to the UVWO terminals as
shown in Figure 16.
BLACK
Figure 16. UVWO Terminal Lugs
Single-Phase 240-Volt Connections
Single-Phase 120-Volt
UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 240-volt operation as shown in Figure 14.
2. Select an output of 208 volts on the digital controller
to obtain 120 volts at the UVWO terminals.
3. Connect the load wires to the UVWO terminals as
shown in Figure 17.
Figure 17. UVWO Terminal Lugs
Single-Phase 120-Volt Connections
NOTICE
BE USED
To obtain single-phase, 120-volt output, the voltage
change-over board must be in the 3-phase, 240/139-volt
position and the voltage on the digital controller must
be set to 208 volts.
BLUE
RED
U
V
W
240V
240V
240V
SINGLE-PHASE
240 VAC (LOAD CONNECTIONS)
BLUE
BLACK
RED
U
V
W
120V
120V
SINGLE-PHASE
120 VAC (LOAD CONNECTIONS)
GREEN
WHITE
O
GROUND
CONNECTION
MUST
BE USED
AT ALL TIMES
GREEN
WHITE
O
120V
GROUND
CONNECTION
MUST
BE USED
AT ALL TIMES