OUTPUT TERMINAL PANEL
The Output Terminal Panel (Figure 14) shown below is
provided for the connection of electrical loads. Lift up on
the cover to gain access to receptacles and terminal lugs.
NOTICE
Terminal legs "O" and "Ground" are considered bonded
grounds
PAGE 30 — DCA300SSJU4F2/F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #2 (04/18/22)

OUTPUT TERMINAL PANEL FAMILIARIZATION

300
U
V
W
W
1Ø AND 3Ø,
NEUTRAL
GROUND
480 -120 VAC
TERMINAL
TERMINAL
OUTPUT TERMINALS
HARD WIRE
HOOKUP PANEL
U
V
W
O
BLACK
RED
BLUE WHITE GREEN
CS-6369 TWIST-LOCK
RECEPTACLES (3)
240Y/139, 50 AMPS
W
CS-6369
TWIST-LOCK
Figure 14. Output Terminal Panel
OUTPUT TERMINAL FAMILIARIZATION
The "Output Terminal Panel" (Figure 14) is provided with
the following:
„ Three (3) 240/139V output receptacles @ 50 amp
„ Three (3) Circuit Breakers @ 50 amps
„ Two (2) 120V GFCI receptacles @ 20 amp
„ Two (2) GFCI Circuit Breakers @ 20 amps
„ Eight (8) Output Terminal Lugs ( U, V, W, O, Ground)
Y
X
GFCI RECEPTACLES (2)
120V, 20 AMP
DCA300SSJU4F3
MODEL SHOWN
CIRCUIT BREAKERS
FOR GFCI RECEPTACLES
CIRCUIT BREAKERS
FOR CS-6369 TWIST
LOCK RECEPTACLES