ENGINE BLOCK HEATER
AND INTERNAL BATTERY CHARGER
120 VAC INPUT RECEPTACLES
This generator comes equipped with an engine block
heater. An internal battery charger is available as an
option. These components are provided with electrical
power cords to connect to a commercial power source.
The engine block heater and internal battery charger both
require 120 VAC in order to operate. A receptacle (Figure 83)
has been provided on the output terminal panel to allow
commercial power to be applied.
These units will ONLY function when commercial power
has been supplied to them (Figure 83).To apply commercial
power to these receptacles, a power cord of adequate size
will be required (see Table 8).
Figure 83. Battery Charger (Option) and Engine Block Heater
PAGE 58 — DCA300SSJU4F2/F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #2 (04/18/22)
ENGINE BLOCK
HEATER
120 VAC INPUT
RECEPTACLE
When using the generator in hot climates there is no reason
to apply power to the engine block heater. However, if the
generator will be used in cold climates it is always a good
idea to apply power to the engine block heater at all times.
If the generator will be used daily, the battery should
normally not require charging. If the generator will be idle
(not used) for long periods of time, apply power to the
battery charger receptacle via commercial power using a
power cord of adequate size.
NOTICE
If the generator will be idle (not used) for long periods
of time and to ensure adequate starting capability,
always have power applied to the generator's internal
battery charger.
ENGINE BLOCK
HEATER
!
OUTPUT TERMINAL
PANEL ASSEMBLY
BATTERY CHARGER
120 VAC INPUT
RECEPTACLE
MAINTENANCE
BATTERY CHARGER
TO CHASSIS
GROUND
GREEN 16 AWG.
TO STARTER "B"
TERMINAL
RED 16 AWG.