Installation; Clearances To Combustibles; Mantel Clearances; Gas Connection - Regency GFi750 Owners & Installation Manual

Table of Contents

Advertisement

Clearances to Combustibles

Minimum Clearances to Combustibles
From Unit
Sides
A
Ceiling
B
Mantel
C
Max. Mantle Depth E
Min. Alcove Width
F
Max. Alcove Depth G
*No hearth required.

Mantel Clearances

254
203
152 102
305
51
559
305 mm Mantel
508
457
406
89 mm
Mantel
356
305
535 mm
254
203
330 mm
152
102
51
0
560 mm
to floor
• A non-combustible mantel may be in-
stalled at a lower height if the framing
is made of metal studs covered with a
non-combustible board.
• The non-combustible mantle when
installed at a lower overall height may
not be lower than 152 mm from the
top of the fireplace opening.

Gas Connection

GAS CONNECTION WARNING:
Only persons licensed to work
with gas piping may make the
180 mm
necessary gas connections
1205 mm
330 mm
305 mm
(see Dia. 2)
1) If the appliance is to be installed into an existing
1220 mm
chimney system, thoroughly clean the masonry
915 mm
fireplace.
2) The appliance is provided with an opening on
the right hand side of the control compartment.
The 9.5 mm flexible gas hose provided needs
to be brought in from behind this opening.
Ensure all gas connections are tight.
3) Locate the center point where the vent will pass
through the chimney above the appliance. Move
the appliance into the exact location where it is
to be installed. Ensure that the Insert is level.
6
NOTE: Shut off valve must be installed in an
accessible location.

Flueing

DO NOT USE AN UNLINED
MASONRY CHIMNEY AS THE
FLUE FOR THIS APPLIANCE.
THE APPLIANCE MUST NOT
CONNECT TO A CHIMNEY
FLUE SERVING A SEPARATE
SOLID FUEL BURNING
APPLIANCE AND MUST BE
TERMINATED TO THE
Top
Faceplate
This appliance is designed to be attached to two
co-linear aluminium flex pipes running the full length
of the chimney. The flue length must be a minimum
length of 2.44 m and a maximum of 10.7 m. See
chart for minimum distances from roof. Periodically
check that the vent is unrestricted.
Side View
Masonry chimneys may take various contours which
the flexible liner will accommodate. However, keep
the flexible liner as straight as possible, avoid
unnecessary bending.
The Air Intake pipe must be attached to the inlet
air collar of the adaptor.
to this appliance.
WARNING
OUTDOORS.
946-773 Vertical Flue Kit
The flue kit contains the following:
Part #
Description
948-305
76mm Flex - 10.7m
948-336
102mm Flex - 10.7m
46DVA-VCH
Termination Cap High Wind
46DVA-34CLTA
Adaptor & Chimney Plate
Flashing
#948-305
#948-305
Gas
Inlet
Note: When installing the flueing, identify the
flues. Mark one exhaust and one intake
Regency IG34 Gas Inbuilt Fireplace
as indicated on the top of the unit.
Flue Restrictor Settings:
29 mm x 2 (Factory Set)
Regency GFi750 Gas Inbuilt Fireplace

installation

#46DVA-VCH
#46DVA-34CLTA
#948-336
|
9