Interfaces
3.7 PROFIBUS DP interfaces
Interface assignment for X136
Table 3- 18
Pin
1
2
3
4
5
6
7
8
9
The 1P5 voltage is provided exclusively for the bus terminal.
No OLPs are permitted.
Signal type: VO = Voltage output (power supply) O = Output B = Bidirectional
Connectable devices
The following devices can be connected to the PROFIBUS DP interfaces:
● PG / PC
● SIMATIC HMI devices
● SIMATIC controllers with PROFIBUS DP interface
● Distributed I/O
● Teleservice adapter
● Drive units with PROFIBUS DP interface (standard slaves)
Note
A teleservice adapter can only be connected to one of the two interfaces.
A detailed, regularly updated list of the modules approved for use with SIMOTION, as
well as notes on their use, can be found on the Internet at
(http://support.automation.siemens.com/WW/view/en/11886029):
Take note of the documentation on the individual modules or devices!
58
PROFIBUS DP interface X136
Signal name
Signal type
--
--
M
VO
2RS_DP
B
2RTS_DP
O
1M
VO
1P5
VO
P24_SERV
VO
2XRS_DP
B
--
--
Meaning
Reserved, do not use
Ground to P24_SERV
RS-485 differential signal
Request to send
Ground to 1P5
5 V power supply for bus terminal, external, short-circuit
proof
24 V for teleservice, short-circuit proof, 150 mA maximum
RS-485 differential signal
Reserved, do not use
SIMOTION D4x5-2