Siemens SIMOTION D4 Series Manual page 44

Hide thumbs Also See for SIMOTION D4 Series:
Table of Contents

Advertisement

Interfaces
3.3 Ethernet interfaces
Note
The two interfaces support Industrial Ethernet (IE). The designation of the interfaces
PN/IE-NET or PN/IE has already been designed for the support of PROFINET basic services
(e.g. DCP, LLDP, SNMP) via these interfaces in a future version. These PROFINET basic
services provide uniform functions for the address assignment and diagnostics, but do not
provide PROFINET IO communication for the connection of drives or I/O modules, for
example.
Additional references
Detailed information on the states of the status LEDs can be found in the
Commissioning and Hardware Installation Manual, Diagnostics chapter.
Interface characteristics
Table 3- 5
Characteristic
Connector type
Cable type
Max. cable length
Autocrossing
Dust protection blanking
plugs for sealing unused
Ethernet ports
Miscellaneous
Pin assignment
Table 3- 6
Ethernet interfaces (X120 P1 and X130 P1)
Pin
Assignment in 10/100 Mbit mode
Signal name
1
TXP
2
TXN
44
X127 P1 and X130 P1
Type
RJ45 socket connector
Industrial Ethernet cable
100 m
Yes
Five blanking plugs contained in the D4x5-2 scope of delivery
Blanking plugs (50 pcs) order number: 6SL3 066-4CA00-0AA0
X127 P1 and X130 P1 are full-duplex 10/100/1000 Mbit/s Ethernet
ports
Signal type
Meaning
1)
O
Ethernet
transmit
differential
signal
O
Ethernet
transmit
differential
signal
4- and 8-wire cables can be used for 10/100 Mbit/s
8-wire cables must be used for 1000 Mbit/s
Assignment in 1 Gbit mode
Signal name
DA+
DA-
SIMOTION D4x5-2
Signal type
Meaning
1)
B
Bidirectional
pair A+
B
Bidirectional
pair A-
SIMOTION D4x5-2
Manual, 11/2010

Advertisement

Table of Contents
loading

Table of Contents