Section 7

Programming

This section of the manual describes how to manually program the control panel from the
built-in annunciator. Each subsection discusses these menu options in detail. All options
described in this section can be performed using the 5660 Silent Knight Software Suite
(SKSS).
Before any customized programming is done, JumpStart should be run first. After
JumpStart is run, thoroughly test the system. The reason the system should be tested
after JumpStart is because Jumpstart automatically programs the system, searching for
and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm
the integrity of the installation prior to performing any custom programming. After
determining that the hardware is properly installed, custom programming can be
performed. Refer to Section 6.
7.1

UL 864 Programming Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES: This product incorporates field programmable software. In
order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Programming Option
Phone Lines
Misc Options 1
7.2

Modules

This section lists the options available under the module option in the program menu. The
following modules are available for the control panel: 5815XL SLC expander, 5860 remote
fire alarm annunciator, 5824 serial/parallel printer interface module, 5496 intelligent power
module, 5895XL intelligent power module, 5880 LED I/O module, and 5865 LED
annunciator.
151209
Important!
Permitted in
Menu Item
UL 864 (Y/N)
Enable Gnd Start
Low AC Report Delay
firealarmresources.com
Possible
Settings
No
Yes & No
Yes
0–30 hours
Settings Permitted in
UL 864
No