IntelliKnight 5820XL Installation Manual

10.3 Built-in Troubleshooting and Testing Tools

The fire control panel has several built-in testing and troubleshooting tools that can be utilized
to save time while testing and troubleshooting points and SLC devices.

10.3.1 SLC Device Locator

SLC device locator can be used to locate a device on a SLC loop.
Follow these steps to locate a particular SLC device:
1. Select
(Point Functions) from the Main Menu.
2
2. Select
(SLC Dev Locator).
4
A message similar to the one shown in Figure 10-1 will display.
3. Press the
or
If NO is chosen you will exit back to the Point Function menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.
4. Select the SLC loop.
5. Enter the SLC address of the device you wish to locate.
The LED on the selected device will start flashing.
6. Press any key to exit SLC device locator function.
Note: Once you exit the system will resume normal operation.
10-4
Figure 10-1 Shut Down Warning
arrow to toggle NO to YES then press
firealarmresources.com
.