Honeywell Silent Knight IntelliKnight 5820XL Installation And Operation Manual page 97

Addressable fire system
Table of Contents

Advertisement

3. From the next menu, select
4. The message "WARNING Will DELETE all system options" displays on the LCD. Select
Yes to continue. A series of messages displays for the next several seconds. JumpStart
scans the SLC loops for devices. This can take several minutes, depending on the number
of devices attached.
5. When the message "Configuring System Done" displays, press any key to continue.
6. Select one of the following options from the menu that displays.
1
- Review System
2
- Repeat JumpStart
3
- Accept Configuration
4
- Enter Programming
151209
for JumpStart.
6
Press
1
if you need to review the JumpStart configuration.
Press
2
if you need to rerun JumpStart for any reason.
1. If you are ready to make the JumpStart configuration permanent, select
2. The system will ask you if the installation contains duct detectors. If there
are none, select
2
for No and skip to Step 8. If the system contains duct
detectors, select
1
for Yes and continue with Step 3.
3. From the list that displays, select the 5815XL device that contains the duct
detectors.
4. The first photoelectric or ionization detector on the system will display.
1
2
Select
for DUCT and
5. Press
to select the next detector. Select
DUCT. Continue until all duct detectors have been selected. (Note: You can
move backwards through the list with
6. When you reach the last detector on this device, press
7. The system will ask you if there are more duct detectors in the system. If
1
there are, select
for Yes and repeat from Step 3. If there are no more
duct detectors, select
2
for No and continue with Step 8.
8. The system will restart in 10 seconds. You can press
ately. Do not select
2
for System Diagnostics. (This feature is for use in
testing at the factory.)
9. After the system resets, it will use the new JumpStart configuration.
If you want to go directly to Program Mode to configure any devices, press
4
. The Programming Menu appears and you can begin programming.
firealarmresources.com
Programming Overview
for NonDUCT.
1
for DUCT and
.)
.
1
to restart immedi-
3
.
2
for Non-
6-3

Advertisement