7.6.4

Miscellaneous Options 1

Through this programming option you can set the water flow delay time, low AC report delay,
enable or disable automatic daylight savings time adjustment, clock format, and AC clock
frequency.

7.6.4.1 Water Flow Delay

You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction
with a water flow switch. The delay is system-wide. All water flow switches on the system
will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1. Enter the installer code.
2. Press
to display the main menu.
or
3. Select
for Program Menu.
7
Display reads:
4. Select
for System Options.
5
5. Select
for Miscellaneous Options 1.
5
A screen similar to the one shown in Figure 7-16 will display.
Figure 7-16 Water Flow Delay Programming Screen
7-38
Initializing
Please wait . . .
firealarmresources.com
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)