Mitsubishi Electric FR-E5NP Instruction Manual page 22

Transistorized inverter
Table of Contents

Advertisement

Pr. 340
Operation Mode
Setting
Pr. 79
0
PU or network operation
1
PU operation
2
Network operation
External/PU combined
3
operation
External/PU combined
4
operation
10
Switch-over
6
7
PU operation interlock
Operation mode switch-
8
over by the external signal
When "0" or "6" is set in Pr. 79 when Pr. 340 = "10", the operation can be switched between the PU
operation and the network operation from the operation panel or the parameter unit (FR-PU04).
• Operation panel
Use
display on the operation mode switching menu to change the operation mode to the PU
operation mode and
• FR-PU04
Use
to change the operation mode to the PU operation and
Mode at Power On or at Restoration
Inverter operates in the network operation mode.
Operation mode can be switched between the PU operation and the
network operation.
Inverter operates in the PU operation mode.
Inverter operates in the network operation mode.
Inverter operates in the external/PU combined operation mode.
Input running frequency from the PU and the start signal from outside.
Inverter operates in the external/PU combined operation mode.
Input running frequency from outside and the start signal from the PU.
Inverter operates in the network operation mode.
Operation mode can be switched between the PU operation and the
network operation.
MRS signal ON .......... Inverter operates in the external operation mode.
MRS signal OFF ........ Inverter operates in the external operation mode.
X16 signal ON............ Inverter operates in the external operation mode.
X16 signal OFF.......... Inverter operates in the PU operation mode.
display to the network operation mode.
15
from Instantaneous Power Failure
(Operation mode can be switched to the PU
operation mode by the parameter unit.)
to the network operation.
INVERTER SETTING