INVERTER SETTING
Pr. 340
Operation Mode
Setting
Pr. 79
0
PU or network operation
1
PU operation
2
Network operation
External/PU combined
3
operation
External/PU combined
4
operation
1
Switch-over
6
7
PU operation interlock
Operation mode switch-
8
over by the external signal
Mode at Power On or at Restoration
from Instantaneous Power Failure
Inverter operates in the network operation mode.
(Profibus master module need not be used for switching)
Inverter operates in the PU operation mode.
Inverter operates in the network operation mode.
(Profibus master module need not be used for switching)
Inverter operates in the external/PU combined operation mode.
Input running frequency from the PU and the start signal from outside.
Inverter operates in the external/PU combined operation mode.
Input running frequency from outside and the start signal from the PU.
Inverter operates in the network operation mode.
Operation mode is switched while running.
Refer to page 16 for details.
MRS signal ON .......... Inverter operates in the network operation mode.
(Operation mode can be switched to the external
operation mode by the program.)
MRS signal OFF ........ Inverter operates in the external operation mode.
X16 signal ON............ Inverter operates in the network operation mode.
(Operation mode can be switched to the external
operation mode by the program.)
X16 signal OFF.......... Inverter operates in the PU operation mode.
14