INVERTER SETTING
(4) Switch-over mode
You can select between PU operation, external operation and network operation.
Operation Mode
Switching
External operation to PU
operation
External operation to
network operation
PU operation to external
operation
PU operation to network
operation
Network operation to
external operation
Network operation to PU
operation
Switching Operation/Operating Status
Change the operation mode to the PU operation mode from the operation panel or
parameter unit.
Rotation direction is the same as that of external operation.
Set frequency is as set by the potentiometer (frequency setting potentiometer).
(Note that the setting will disappear when power is switched off or the inverter is reset.)
Mode change command to the network operation mode is transmitted from the network.
Rotation direction is the same as that of external operation.
Set frequency is as set by the potentiometer (frequency setting potentiometer).
(Note that the setting will disappear when power is switched off or the inverter is reset.)
Press the external operation key of the parameter unit.
Rotation direction is determined by the external operation input signal.
Set frequency is determined by the external frequency setting signal.
Mode change command to the network operation mode is transmitted from the network.
Rotation direction and set frequency are the same as those of PU operation.
The switch-over command to the external operation mode is sent from the network.
Rotation direction is determined by the external operation input signal.
Set frequency is determined by the external frequency setting signal.
Select the PU operation mode with the operation panel or parameter unit.
Rotation direction and set frequency are the same as those of network operation.