INVERTER SETTING
(2) Operation mode switching method
Symbol
Switching Type
PU operation → External operation
A
External operation → PU operation
B
External operation → Network operation
C
Network operation → External operation
D
PU operation → Network operation
E
Network operation → PU operation
F
*1 In the switch-over mode (Pr. 79 = 6) or when Pr. 340 = "10", switching in E and F is allowed. (Refer to page 16.)
CAUTION
1. When "1" or "10" is set in Pr. 340 "link startup mode selection", the operation mode is network
operation at power on or inverter reset.
2. When setting "1" or "10" in Pr. 340, the initial settings of the inverter must be made.
Switched via
Profibus master module
C
Network
operation
D
Switched
from PU
A
External
PU operation
operation
B
E
F
(Switching disallowed)
Switching Method
Operate the external operation key on the PU.
Operate the PU operation key on the PU.
Switched to the network operation mode via Profibus master
module.
Switched to the network operation mode via Profibus master
module.
Switching disallowed. Allowed if external operation is selected
in A and network operation is then selected in C. *1
Switching disallowed. Allowed if external operation is selected
in D and PU operation is then selected in B. *1