4 SET-UP AND PROCEDURE BEFORE OPERATION
b15
The upper byte is basically ignored. However, a switch setting error (0180h)
will occur during hardware test if the upper byte is other than 0.
4 - 47
(b)
Battery error detection setting (bit 2)
This setting is provided to determine whether battery error detection is
enabled or not while the Web server module is operating without battery.
(Refer to Section 4.11.)
0 : Detects battery error.
1 : Not detect battery error.
(c)
Logging monitor setting (bit 4)
Whether the latest file update time is displayed or not in the file
specification field of the logging monitor is set in this setting. (Refer to
Section 6.2.3.)
0 : Not display the latest file update time.
1 : Displays the latest file update time.
POINT
(1) Regardless of the logging monitor setting, the logging file time information can be
obtained from the file name. (Refer to Section 6.4.4 (2) (h).)
(2) When the logging monitor setting is "1", longer time will be required to display the
logging monitor if there are many logging files saved.
(3) Response monitoring time setting (switch 3 (lower byte))
This is the setting for timeout time (second) from when a module sends a request
to the CPU of the accessed device until the CPU responds to it.
Response timeout error will occur if the CPU of the accessed device does not
respond to the request after the set time has passed.
Setting range: 15 to 255 (second)
Response monitoring time will be automatically default value (15 seconds) if it is
not set or set to any of 0 to 14.
to
b8 b7
(Upper byte)
Specify 0.
(default value: 15 seconds)
to
b0
(lower byte)
Switch 3
MELSEC-Q
Response monitoring time setting
15 to 255 (seconds)
Response monitoring time will be
automatically default value (15 seconds)
if it is not set or set to any of 0 to 14.
4 - 47