■ Characteristics
Item
Accuracy of operating
time
Setting error
Influence of voltage
Influence of temperature
Cyclic error
Memory protection
Insulation resistance
Dielectric strength
Noise immunity
Vibration
Destruction 10 to 55 Hz with 0.375-mm single amplitude in 3 directions for 2 hours each
resistance
Malfunction 10 to 55 Hz with 0.25-mm single amplitude in 3 directions for 10 minutes each
Shock
Destruction 300 m/s
resistance
Malfunction 100 m/s
Life
Mechanical
expectancy
Electrical
Approved standards
EMC
Weight
Note: 1. The total error including the repeat accuracy, setting error, variation due to voltage change, and variation due to temperature change is
±0.01% ±0.05 s max.
2. The total time when power is not being supplied.
Downloaded from
Elcodis.com
electronic components distributor
Weekly 2-circuit Models
(H5S-W@2)
±0.01%±0.05 s max. (See note 1.)
The ±0.01% value applies to the set time interval.
±15 s per month (at 25°C)
Continuous use: 5 years min. (at 25°C) (See note 2.)
100 MΩ min. (between current-carrying terminals and exposed non-current carrying metal parts, between operation
circuit and control output circuit, between control output circuits, and between non-continuous contacts.)
2,950 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between operation circuit and control output circuit, and between control output
circuits)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
±1,500 V (between power terminals, for AC power models), ±500 V (between power terminals, for DC power models)
Square-wave noise by noise simulator (pulse width: 100 ns, for 1 µs, 1-ns rise time)
2
3 times each in x, y, and z axes, 6 directions
2
3 times each in x, y, and z axes, 6 directions
100,000 operations min.
50,000 operations min. (15 A at 250 VAC, resistive load)
50,000 operations min. (10 A at 30 VDC, resistive load)
50,000 operations min. (10 A at 250 VAC, inductive load (cosφ = 0.7))
50,000 operations min. (1 HP at 250 VAC, motor load)
50,000 operations min. (100 W at 100 VAC, lamp load)
10,000 operations min. (300 W at 100 VAC, lamp load)
UR
: UL 508/CSA C22.2 No.14,
C
US
Conforms to EN 60730-2-7(Pollution degree 2/overvoltage category II),
Conforms to VDE 0106/part100.
Conforms to Electrical Appliance and Material Safety Law (for Japan)
(EMI)
EMI Radiated:
EMI Conducted (Continuous):
EMI Conducted (Non-continuous):
Harmonic Current:
Voltage fluctuation/flicker:
(EMS)
ESD Immunity:
Radiated Electromagnetic Field Immunity: EN 60730-2-7 (IEC 61000-4-3): 10-V/m AM modulation
Conducted Disturbance Immunity:
Burst Immunity:
Surge Immunity:
Voltage Dip/Interrupting Immunity:
Approx. 200 g
Yearly 2-circuit Models
(H5S-Y@2)
±15 s per month (at −10 to 45°C), ±20 s per month (at 45 to 55°C)
EN 60730-2-7
EN 60730-2-7 (CISPR 22 Class B)
EN 60730-2-7 (CISPR 22 Class B)
EN 60730-2-7 (CISPR 14-1)
EN 60730-2-7 (IEC 61000-3-2 Class A)
EN 60730-2-7 (IEC 61000-3-3)
EN 60730-2-7
EN 60730-2-7 (IEC 61000-4-2): 6 kV contact discharge
EN 60730-2-7 (IEC 61000-4-6): 10 V (0.15 to 80 MHz)
EN 60730-2-7 (IEC 61000-4-4): 2 kV power line
EN 60730-2-7 (IEC 61000-4-5): 1 kV line to line (power line, output line)
EN 60730-2-7 (IEC 61000-4-11): 0.5-s cycle, 100% (rated voltage)
H5S
Yearly 4-circuit Models
(H5S-Y@4)
50,000 operations min. (3 A at
250 VAC, resistive load)
50,000 operations min. (3 A at
30 VDC, resistive load)
8 kV air discharge
(80 MHz to 1 GHz, 1.4 GHz to 2 GHz)
10-V/m pulse modulation (900 MHz)
1 kV control line
2 kV line to ground (power line, output
line)
0.5 kV line to line (input line)
1 kV line to ground (input line)
4