Connecting The Unit Power Supply - Omron E3NX-FA Operation Manual

Ethercat digital sensor communication unit
Table of Contents

Advertisement

4-3-3

Connecting the Unit Power Supply

Connect a cable from the 24-VDC unit power supply to the unit power supply connector on each Slave
Unit, and supply power to individual Slave Units.
Mount a pin terminal, or equivalent to the unit power supply cable so that it will not be displaced.
Do not wire a power supply to the communications path of the Distributed Sensor Units. The Units may
be damaged.
 Recommended product
The following pin terminals are recommended for the unit power supply cables.
Model
AI0,5-10WH
H0.5/16 orange
Also, the following screwdriver is recommended for removing pin terminals.
Model
XW4Z-00C
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
+V Terminal
−V Terminal
Applicable wire size
CRIMPFOX UD6
(Product No. 1204436)
2
0.5 mm
/AWG20
or CRIMPFOX ZA3
series
Crimper PZ1.5
2
0.5 mm
/AWG20
(Product No. 900599)
Manufacturer
OMRON
4 Installation and Wiring
Unit Power
Supply Cable
To Unit DC24V
Pin Terminal
Power Supply
Crimping tool
Phoenix Contact
Co., Ltd.
Weidmueller Japan Co., Ltd.
Manufacturer
4 - 9
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents