Preparation For Connecting Network - Omron E3NX-FA Operation Manual

Ethercat digital sensor communication unit
Table of Contents

Advertisement

4-2-2

Preparation for Connecting Network

Prepare the following devices.
Product name
Twisted-pair cable
(Cables with connectors
below are also allowed.)
RJ45 connector
Precautions for Correct Use
• The maximum cable length between connected nodes is 100 m. Note that some cables do not
guarantee 100 m. In general, if the conductors are strand wire, the transmission performance
will be lower than solid wire and the operation at 100-m distance cannot be guaranteed.
Confirm details with the cable manufacturer.
• When selecting connectors, check that the cables to be used conform to connectors. Items to
be checked include conductor size, conductor wire type (solid wire/twisted wire, 2/4 pairs), and
outer diameter.
Reference
We recommend cables with double, aluminum tape and braided shielding, taking noise
resistance into consideration.
 Recommended Parts
The recommended products for the parts described above are listed below.
• Sizes and Conductor Pairs: AWG 24 × 4 Pairs
Communications Cables
Connectors
• Sizes and Conductor Pairs: AWG 22 × 2 Pairs
Communications Cables
Connectors
We recommend that you use combinations of the above Cables and Connectors.
(Notes)
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
100BASE-TX (Category 5 or higher)
Double-shield (aluminum tape + braided shielding)
Category 5 or higher
Shielded
Part
Tonichi Kyosan Cable, Ltd.
Kuramo Electric Co., Ltd.
SWCC Showa Cable Systems Co. Ltd.
Panduit Corporation
Part
Kuramo Electric Co., Ltd.
OMRON Corporation
Comment
Manufacturer
Manufacturer
4 Installation and Wiring
Model
NETSTAR-C5E SAB 0.5×4P
KETH-SB
FAE-5004
MPS588
Model
KETH-PSB-OMR
XS6G-T421-1
4
4 - 5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents