Clearances - Regency Panorama P36E-NG11 Owners & Installation Manual

Zero clearance direct vent gas fireplace
Table of Contents

Advertisement

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fireplace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back
Side
Floor
NOTE: The minimum floor clearance must be maintained from the top surface of the carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Ceiling from top of unit.
Side Wall Clearances:
* Measured from edge of unit. See the "Regency Clearances for dimensions" section.
Horizontal Vent Clearances:
Top
Side
Bottom
Vertical Vent Clearances
Alcove Clearances**:
Max. Depth
Min. Width
Min. Height
WARNING: Fire hazard is an extreme risk if these clearances are not adhered to.
The HeatWave Duct Kit has different
clearance and framing requirements,
check the HeatWave manual for details.
0"
(0mm)
0"
(0mm)
0"
(0mm)
32"
(1016mm)
6"*
(152mm)
2"
(51mm)
1-1/2" (38mm)
1-1/2" (38mm)
1-1/4" (32mm)
36"
(914mm)
48"
(1219mm)
72"
(1829mm)
P36E-11 Zero Clearance Direct Vent Gas Fireplace