Regency P36E-NG4 Owners & Installation Manual

P36e zero clearance direct vent gas fireplace
Table of Contents

Advertisement

WARNING:
If the information in these instructions are not followed exactly, a fi re
or explosion may result causing property damage, personal injury or
loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable vapors and liquids in the
vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed installer, service
agency or the gas supplier.
FOR YOUR SAFETY
Tested by:
918-852a
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
P36E Zero Clearance
Direct Vent Gas Fireplace
MODELS:
P36E-NG4 Natural Gas
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
P36E-LP4 Propane
Owners & Installation Manua
What to do if you smell gas:
 Do not try to light any appliance
 Do not touch any electrical switch: do not
use any phone in your building.
 Immediately call your gas supplier from
a neighbour's phone. Follow the gas
supplier's instructions.
 If you cannot reach your gas supplier, call
the fi re department.
l
04/08/13

Advertisement

Table of Contents
loading

Summary of Contents for Regency P36E-NG4

  • Page 1 P36E Zero Clearance Direct Vent Gas Fireplace MODELS: P36E-NG4 Natural Gas P36E-LP4 Propane Owners & Installation Manua What to do if you smell gas: WARNING:  Do not try to light any appliance If the information in these instructions are not followed exactly, a fi re ...
  • Page 2 To the New Owner: Congratulations! You are the owner of a state-of-the-art Gas Fireplace by FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. The P36E has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch. The model P36E has been approved by Warnock Hersey for both safety and effi...
  • Page 3 INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE This FPI product has been tested and listed by Warnock Hersey as a Vented Gas Fireplace Heater to the following standards: CAN/CGA-2.17- M91, and ANSI Z21.88-2009/CSA 2.33-2009. This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada.
  • Page 4: Table Of Contents

    Heatwave Duct System ..........10 Aeration Adjustment ............52 Heat Release kit ............10 Normal Operating Sounds Of Gas Appliances ....53 Clearances ..............11 Copy of the Lighting Plate Instructions ......53 Regency Clearances ..........12 ® Tripoli Screen Door Clearances ......12 MAINTENANCE Hampton Clearances .........12 ®...
  • Page 5 TABLE OF CONTENTS REGENCY OPTIONS ® Flush Trim ..............56 Flush Louvers ..............56 Double Screen Door ............56 Bay Door..............57 Bay Trim ..............57 Bay Louvers..............57 Finishing Trim...............58 Full Screen doors Installation........59 Tripoli Screen Door ............61 HAMPTON OPTIONS ® Hampton Cast Faceplate ...........63 ®...
  • Page 6: Safety Label

    SAFETY LABEL This is a copy of the label that accompanies each P36E Zero Clearance Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review. The safety label is located on the front inside base of the unit, visible when the bottom louver is open.
  • Page 7: Requirements

    REQUIREMENTS MA Code - CO Detector (for the State of Massachusetts only) 5.08: Modifications to NFPA-54, Chapter 10 (2) Revise 10.8.3 by adding the following additional requirements: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:...
  • Page 8: Dimensions

    DIMENSIONS UNIT DIMENSIONS 33-1/4” (838mm) 36” (914mm) 36” (914mm) 12-3/4” (324mm) HAMPTON FACEPLATE DIMENSIONS 43-1/4” (1099mm) 1-1/4” (32mm) 32-1/4” (819mm) P36E-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 9: Installation

    INSTALLATION IMPORTANT MESSAGE GENERAL SAFETY 12) Installation and any repairs to this appliance should be done by a qualifi ed service per- SAVE THESE INFORMATION son. A professional service person should INSTRUCTIONS be called to inspect this appliance annually. 1) The appliance installation must conform Make it a practice to have all of your gas with local codes or, in the absence of local appliances checked annually.
  • Page 10: Locating Your Gas Fireplace

    Optional Brick Panels c. Log Set Installation DUCT SYSTEM d. Standard Flush Door OPTIONAL KIT #946-556 e. Regency Flush or Bay Fronts f. Hampton Cast Faceplate g. Remote Control The HeatWave Air Duct Kit increases the h. Wall Switch effectiveness of your fi...
  • Page 11: Clearances

    A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fi replace and vent system be installed only in accordance with these instructions. IMPORTANT: See the "Regency Tripoli Screen Door Series Framing Note" section for framing note on Tripoli Screen Door. Clearance to Combustibles from: Back 0"...
  • Page 12: Regency ® Clearances

    INSTALLATION REGENCY CLEARANCES ® Clearances for Bay Front, Flush Front & Full Screen Doors TRIPOLI SCREEN HAMPTON CLEARANCES ® DOOR CLEARANCES P36E-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 13: Regency Series Combustible Mantel Clearances

    INSTALLATION REGENCY SERIES COMBUSTIBLE MANTEL CLEARANCES ® Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible board. Because of the extreme heat this fi replace emits, the mantel clearances are critical.
  • Page 14: Hampton ® Combustible Mantel Clearances

    INSTALLATION TRIPOLI SCREEN DOOR COMBUSTIBLE MANTEL CLEARANCES Because of the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from top of unit are shown in the diagram below. Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible board.
  • Page 15: Mantel Leg Clearances

    INSTALLATION REGENCY ® MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram: Maximum 1-1/2" projection at 2" minimum clearance. HAMPTON MANTEL LEG CLEARANCES ® Combustible mantel leg clearances as per diagram: Hampton Cast Faceplate Width: 43-1/4" Maximum 1-1/2" projection at 2"...
  • Page 16: Framing And Finishing

    INSTALLATION FRAMING AND FINISHING 2) Frame in the enclosure for the unit with IMPORTANT FINISHING DETAIL NOTE: 3) For exterior walls, insulate the enclosure to framing material. The framed opening is When installing tile, carpeting, or any other the same degree as the rest of the house, fi...
  • Page 17: Regency Tripoli Screen Door Series Framing Note

    INSTALLATION REGENCY TRIPOLI SCREEN DOOR SERIES FRAMING NOTE ® When installing the optional Tripoli Screen Door Series, a non-combustible material 12" (305mm) above the unit and 6" (153mm) on each side must be used (see Diagram 2). For complete framing details see page 57.
  • Page 18: Unit Assembly Prior To Installation

    INSTALLATION UNIT ASSEMBLY Top Facing Support & "C" Screw Position: Side Nailing Strips For a facing material depth of 1-1/4" (32mm), PRIOR TO the top facing support must be reversed. INSTALLATION Determine the total thickness of facing material (e.g. drywall plus ceramic tiles) to allow the fi...
  • Page 19: Exterior Vent Termination Locations

    INSTALLATION EXTERIOR VENT TERMINATION LOCATIONS Minimum Clearance Requirements Canada Clearance above grade, veranda, porch, deck, or balcony 12"(30cm) 12"(30cm) Clearance to window or door that may be opened 12"(30cm) 9" (23cm) Clearance to permanently closed window Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm) 18"(46cm) 18"(46cm) from the center line of the terminal (check with the local code)
  • Page 20: Venting

    INSTALLATION VENTING DIRECT VENT SYSTEM (FLEX) HORIZONTAL TERMINATIONS ONLY These venting systems, in combination with the P36E Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in the "Exterior Vent Termination Locations"...
  • Page 21: 4" X 6-5/8" Rigid Pipe Cross Reference Chart

    INSTALLATION 4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI. Description Selkirk American Metal Security ICC Excel Simpson Metal-Fab™ ® Direct Temp™ Products® Secure- Vent®...
  • Page 22 Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard. Regency Fireplace Products 6988 Venture St Delta BC Canada V4G 1H4 604 946 5155 www regency fire com P36E-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 23: Rigid Pipe Venting Systems

    INSTALLATION RIGID PIPE VENTING SYSTEMS Horizontal or Vertical Terminations Flat Wall Installation Wall Thickness Vent Length Required The minimum components required for a basic horizontal termination are: (inches) (inches) 4" - 5-1/2" 6" Horizontal Termination Cap Elbow 7" - 8-1/2" 9"...
  • Page 24: Rigid Pipe Venting Arrangements

    INSTALLATION RIGID PIPE VENTING ARRANGEMENTS HORIZONTAL TERMINATIONS FPI DIRECT VENT SYSTEM (FLEX) (Propane & Natural Gas) The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90 elbow (two 45 elbows equal one 90 elbow). Note: Must use optional rigid pipe adaptor (Part # 510-994) when using Rigid Pipe venting systems. All Rigid Pipe Systems 4"...
  • Page 25 INSTALLATION Horizontal Venting with Two (2) 90 Elbows One 90 elbow = Two 45 elbows. Option H + H1 W i t h t h e s e o p t i o n s , 0' Min. 2' Max. maximum total pipe length 1' Min.
  • Page 26 INSTALLATION Vertical Venting with Two (2) 90 Elbows One 90 elbow = Two 45 elbows. Option V + V1 With these options, 0' Min. 2' Max. 1' Min. max. total pipe length 1' Min. 4' Max. 2' Min. is 30 feet with min. of 6 feet total vertical 2' Min.
  • Page 27: Vertical Terminations

    INSTALLATION RIGID PIPE VENTING ARRANGEMENTS VERTICAL TERMINATIONS (Propane & Natural Gas) The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90 elbow, with Rigid Pipe vent systems for Propane and Natural Gas. •...
  • Page 28 INSTALLATION The P36E is approved for a 40 ft. straight vertical, with rigid pipe vent systems for Propane and Natural Gas, as per the diagram 1. The shaded area in the diagram 1 shows all allowable combinations of straight vertical and offset to vertical terminations with rigid pipe vent systems for Propane and Natural Gas.
  • Page 29: Vertical Termination - Co-Linear Flex System

    INSTALLATION VERTICAL TERMINATION - CO-LINEAR FLEX SYSTEM THE APPLIANCE MUST NOT BE Masonry chimneys may take various contours which the fl exible liner will accommodate. However, CONNECTED TO A CHIMNEY FLUE keep the fl exible liner as straight as possible, avoid unnecessary bending. SERVING A SEPARATE SOLID FUEL BURNING APPLIANCE.
  • Page 30: Venting Arrangements - Vertical Termination

    INSTALLATION VENTING ARRANGEMENTS - VERTICAL TERMINATION with Co-linear Flex System for both Residential & Manufactured Homes into Masonry Fireplaces Horizontal Distance (Feet) The shaded area in the diagrams show the allowable vertical terminations. P36E-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 31 INSTALLATION b) Horizontal runs of vent must be DURA-VENT HORIZONTAL supported every three feet. Wall straps TERMINATIONS are available for this purpose. Install the vent system according to the 5) Mark the wall for a 10" x 10" square hole. The manufacturer's instructions included with center of the square hole should line up with the components.
  • Page 32 INSTALLATION DURA-VENT VERTICAL 4) Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow TERMINATIONS connections are in the fully twist-locked position and sealed. 1) Maintain the 1-1/4" clearances (air spaces) to combustibles 5) Cut a hole in the roof centered on the small when passing through ceilings, drilled hole placed in the roof in Step 2.
  • Page 33: Direct Vent System (Flex) Installation Procedures

    INSTALLATION 4) Separate the 2 halves of the wall thimble and be increased. A poor draft, or down drafting securely fasten the one with the tabs to the can result from high wind conditions near big trees or adjoining roof lines, in these cases, outside wall making sure that the tabs are Note: To make on top and bottom.
  • Page 34: Gas Line Installation

    INSTALLATION GAS LINE P36E-NG4 System Data P36E-LP4 System Data INSTALLATION For 0 to 4500 feet altitude For 0 to 4500 feet altitude Burner Inlet Orifi ce Sizes: #37 The gas line is brought through the right of the Burner Inlet Orifi ce Sizes: #52 appliance.
  • Page 35: Pilot Adjustment

    Note: If you have an incorrect fl ame pattern, contact your Regency dealer for ® 1) Make sure the switch is in the "OFF" position.
  • Page 36: Conversion From Ng To Lp

    INSTALLATION CONVERSION FROM NG TO LP FOR P36E-4 USING SIT 886 GAS VALVE THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !! Remove burner orifi ce with a 1/2" 3b) Remove the Burner Tray by removing Each Kit contains one LPG wrench.
  • Page 37: Optional Brick Panels

    INSTALLATION OPTIONAL BRICK PANELS 4) Install the 2 brick retaining clips, one on each side. 1) Undo the bottom 2 door latches and open and remove glass door. Remove logs. Note: The logs must not be in the unit. 2) Insert the back brick panel fi rst by carefully slipping it between the back wall of the fi...
  • Page 38: Log Set Installation

    INSTALLATION LOG SET INSTALLATION Read the instructions below carefully and refer to the diagrams. If logs are broken do not use the unit until they are replaced. Broken logs can interfere with the pilot operation. The gas log kit (Part # 512-930) contains the following: Place Log 02-49 on the rear log support pins with the fl...
  • Page 39 INSTALLATION Position Log 02-53 across the cutouts in Logs 02-49 and Sit Log 02-50 on the front left side of the burner. Push the 02-51 with the notch on the left side of the log fi tting into back of the log against the 2 front brackets with the notch the 2nd grate tab.
  • Page 40 INSTALLATION 10) Place the embers on the front of the burner tray in the Place Log 02-52 between Logs 02-51 and 02-49 and on places shown on the photo. the indentation on Log 02-54. The bottom right end sits behind the rear grate tab. Separate platinum embers and place on the front burner on and around the embers.
  • Page 41: Standard Flush Door

    INSTALLATION STANDARD FLUSH DOOR The standard fl ush door comes with a black frame. To install the frame, Be careful that the glass gasket does not roll up; there must be a gap simply hook the top door fl ange onto the top of the unit and swing the between the gasket and the door lip to ensure that the door sits securely door towards the unit, see Diagram 1.
  • Page 42: Optional Wall Thermostat

    WALL THERMOSTAT WALL SWITCH REMOTE CONTROL 1) Run up to 10' of wire through the right or Use the Regency Remote Control Kit approved ® A wall thermostat may be installed if desired, left side gas inlet opening. Be careful not for this unit.
  • Page 43: Gt Remote Installation

    INSTALLATION GT REMOTE INSTALLATION 1) Shut off the gas supply and disconnect all power to the unit. 8) Plug in receiver DC supply wire - as shown below. 2) Remove the louvers, bay door or faceplate if installed. 3) Disconnect battery pack - located on the fl oor of the unit, as shown below and discard.
  • Page 44: Gtm Remote Installation

    INSTALLATION GTM REMOTE INSTALLATION 6) Identify wires in the GTM/GTMF remote wiring harness. 1) Shut off the gas supply and disconnect all power to the unit. (see wiring diagram.) 2) Remove the louvers, bay door or faceplate if installed. 7) Connect the TPTH and TH wires - green to green and white to white as shown below.
  • Page 45 INSTALLATION 10) Install the stepper motor in the same location the hi/lo knob was 15) Install 4-AA batteries into the receiver. removed from - with 2 screws as shown below. 16) Bundle all wires together and clip with supplied wire clip - as shown below.
  • Page 46: Gtmf Remote Installation

    INSTALLATION GTMF REMOTE INSTALLATION 7) Connect the TPTH and TH wires - green to green and white to 1) Shut off the gas supply and disconnect all power to the unit. white as shown below. 2) Remove the louvers, bay door or faceplate, if installed. 3) Disconnect battery pack - located on the fl...
  • Page 47 INSTALLATION 11) Install 4 - AA batteries into the receiver. 14) Reinstall the DFC box onto the velcro pad on the fl oor of the unit. 15) Install the heat shield to the receiver with two screws and attach to the fl oor of the unit with a velcro pad. Heat shield 12) Plug ‘motor’...
  • Page 48: Wiring Diagrams

    INSTALLATION WIRING DIAGRAMS This heater does not require a 120V A.C. supply for operation. In case of a power failure, the burner switch and the optional remote control/ thermostat will continue to operate. However, a 120V A.C. power supply is needed for the fan/blower operation. (Do not cut the ground terminal off under any circumstances.) NOTE: Even if the fan is not purchased with the unit, it is still a good idea to bring power to the receptacle box (provided with the unit) in case the fan is installed at a later date.
  • Page 49: Ac Power Adaptor Installtion (For Surefi Re System)

    AC Power Adaptor Installation (For Surefi re System) An optional AC power adaptor may be installed as a constant power source for the SureFire system. NOTE: AC power adaptor is not required when using GTMF Remote IMPORTANT: Recommend removing the 4-AA batteries in the SureFire receiver. This will avoid battery leakage and power drainage.
  • Page 50: Optional Fan Wiring Diagram

    P ower at Stove Wall J unction Box *Speed Control S witch with lead wires Wire Nuts (Regency) 14 AWG wire *Wire C l a mp P36 E lectrical Connec tion Alternative Sc heme " B" , Wire Nuts *Receptacle B ox...
  • Page 51: Operating Instructions

    OPERATING INSTRUCTIONS FAN INSTALLATION 7) Attach the Fan control box to the Burner 12) Secure the fan wires and power cord by ON/OFF control box. attaching one of the adhesive backed wire (OPTIONAL) holder clips (Part #910-199) onto the stove base.
  • Page 52: Operating Instructions

    OPERATING INSTRUCTIONS OPERATING AERATION LIGHTING INSTRUCTIONS ADJUSTMENT PROCEDURE 1) Read and understand these instructions IMPORTANT The air shutter can be adjusted by moving the before operating this appliance. To ignite or reignite the pilot, you adjusting wire up or down. The wire is accessed through the bottom louver opening.
  • Page 53: Normal Operating Sounds Of Gas Appliances

    OPERATING INSTRUCTIONS COPY OF THE LIGHTING PLATE INSTRUCTIONS NORMAL OPERATING SOUNDS OF GAS APPLIANCES FOR YOUR SAFETY READ BEFORE LIGHTING This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or It is possible that you will hear some sounds Natural Gas and Propane Installation Codes, CSA B149.1.
  • Page 54: Maintenance

    MAINTENANCE GLASS GASKET MAINTENANCE 3) Check for evidences of excessive condensation, such as water droplets forming INSTRUCTIONS in the inner liner, and subsequently dripping If the glass gasket requires replacement use out the joints, Continuous condensation can 5/8" fl at glass gasket for the Bay Front (Part cause corrosion of caps, pipe, and fi...
  • Page 55: Removing Valve

    MAINTENANCE 8) Remove the rear log stand by removing the REMOVING VALVE 2 screws. 1) Shut off the gas supply. 9) Remove the 10 screws securing the valve tray assembly in place (Diagram 2) Remove the louvers (and bay door if it is 2) and then lift the entire assembly out on).
  • Page 56: Regency ® Options

    REGENCY OPTIONS ® FLUSH LOUVERS FLUSH TRIM DOUBLE SCREEN DOOR 1) Install the top louver by sliding the two Attach the round magnets to the back of the top bracket clips into the brackets located trim piece and to the bottom trim piece, then 1) Pull out the top louver.
  • Page 57: Bay Door

    REGENCY OPTIONS ® BAY TRIM BAY DOOR 2) Install bottom louver by sliding the two bracket clips into the brackets located underneath the bay door. Secure with 1 Attach 4 supplied magnets each to the back of The Bay louvers MUST be used...
  • Page 58: Finishing Trim

    REGENCY OPTIONS ® FINISHING TRIM NOTE: Remove both the Flush Louvers or Bay Louvers and the Flush Front or Bay Front prior to installing the Finishing Trim. 1) Install the Finishing Trim sides as shown in the diagram, line up the holes in the side trim with the holes in the fi rebox side.
  • Page 59: Full Screen Doors Installation

    REGENCY OPTIONS ® FULL SCREEN DOORS INSTALLATION 1) Before beginning the installation, remove the Screen Doors from the Full Screen Door Frame by fully opening the doors and lifting up off of the hinges. See important note in step 7.
  • Page 60 REGENCY OPTIONS ® 3) Install the hinges to the hinge brackets on the left and right side of the 6) Slide the Top Grill into the louver brackets located on the inside top bottom of the outer frame, secure using 2 x #8 Philips Head Screws of the fi...
  • Page 61: Tripoli Screen Door

    REGENCY OPTIONS ® TRIPOLI SCREEN DOOR When installing the optional Tripoli Screen Door Series, a non-combustible material 12" (305mm) above the unit and 6" (153mm) on each side must be used (see Diagram 1). The Tripoli Screen Door Series also requires steel stud framing above and on each side of the unit (refer to Diagram 1).
  • Page 62 Material Diagram 8 1” Facing Material 9) Optional Install Optional 3-Panel Arch Door. (Refer to Install 3-Panel Arch Door Instruction Sheet). 10) Change in Logo Diagram 5 Replace existing logo with Regency logo. P36E-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 63: Hampton ® Options

    HAMPTON OPTIONS ® HAMPTON CAST FACEPLATE ® 1) Remove top louver. 5) Slide top piece of faceplate into side faceplates by fi tting mounting plates into brackets. 2) Open bottom louver. 3) Install the left side faceplate by pushing in at the side of the fi rebox (Back View) and line up with top and bottom holes on side.
  • Page 64: Hampton ® Cast Grills

    HAMPTON OPTIONS ® HAMPTON CAST GRILLS ® 1) Remove the 3 faceplate mounting phillips head screws from the 5) Install hinge to bracket then secure with screw. inside top of fi rebox, and discard if necessary. Hinge Bracket 2) Place top grill in brackets located inside top of fi rebox as shown. 6) Place something underneath bottom grill to prevent scratching.
  • Page 65: Parts List

    PARTS LIST MAIN ASSEMBLY Part # Description Part # Description Part # Description 948-045 Chain 42) 910-331/P Fan Motor (120 V) 31) * Flue Mounting Plate 948-025 Spring 432-966 Fan Switch Assembly 910-428 Duplex Receptacle 513-901 Brick Panel Set - Standard (120 Volts) (Optional) 910-429 Box - Receptacle...
  • Page 66: Burner Assembly & Log Set

    PARTS LIST BURNER ASSEMBLY & LOG SET Part # Description 513-574E/P Valve Assy - Natural Gas 513-576E/P Valve Assy - Propane 52) * Valve Tray - NG/LP 53) 430-055 Gasket - Valve Access Plate 55) 910-422 HI/LOW 3" Extension Knob 57) 911-004 886 SIT Valve - NG 911-005...
  • Page 67: Regency ® Flush Front Accessories

    PARTS LIST REGENCY FLUSH FRONT ACCESSORIES ® Part # Description Part # Description 132) 512-518 Flush Door Assembly 150) * Flush Glass Trim-Gold 510-920 Flush Louvers - Gold/Black 904-196 Magnet (1" round) 510-922 Flush Louvers - Black 510-947 Flush Glass Trim - Steel (Set)
  • Page 68: Regency ® Bay Front Assembly

    PARTS LIST REGENCY BAY FRONT ASSEMBLY ® Part # Description Part # Description 112) * Bay Front Trim - Top/Bottom 780-931 Bay Front Complete 780-934 Bay Door Trim - Gold 103) 940-092/P Side Glass 113) * Bay Door Trim-Gold-Bottom 107) 936-243...
  • Page 69: Faceplate & Grill Assembly

    PARTS LIST HAMPTON CAST FACEPLATE & GRILL ASSEMBLY Part # Description 513-971** Cast Faceplate (Set) 201) * Cast Faceplate - Right 202) * Cast Faceplate - Top 203) * Cast Faceplate - Left 513-981** Cast Grills (Set) 204) * Top Grill 205) * Bottom Grill *Not available as a replacement part.
  • Page 70 NOTES P36E-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 71: Warranty

    FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI a cturer defect. zed selling dealer is responsible for all in-fi eld service work carried out on your Regency product. FPI will not be liable for results or costs of workm ed service persons or dealers.
  • Page 72 ___________________________________________________________________ Installer: ___________________________________________________________ Phone #: ___________________________________________________________ Date Installed: ______________________________________________________ Serial No.: __________________________________________________________ FPI, Regency®, Hampton Series and SureFire are trademarks of FPI Fireplace Products International Ltd. © Copyright 2011, FPI Fireplace Products International Ltd. All rights reserved. Printed in Canada...

This manual is also suitable for:

P36e-lp4