Circuit Breaker
Voltage
Regulator
Power Switch
(1) Manual Start
Set frequency of the controller. (Refer to section"5-4. Frequency change" )
1
Turn the Circuit Breaker to OFF position.
2
Turn the Power Switch to ON position.
3
< Note >
 When turn the Power Switch to the ON position, the "Low Oil Pressure" warning indicators will
illuminate, but all indicator lights will turn off when the engine is started.
Press the Manual Mode Button.
4
Press the Start Button to start the engine.
5
< Note >
 When the Start Button is pressed, preheating is automatically performed, but preheating is
skipped when the coolant temperature not less than 30 degrees.
 Pre-heating time depends on the coolant temperature.
 Automatically repeats "Crank Attempt" and "Crank Rest" up to 3 times.
 Please keep in mind that the muffler may emit some smoke when engine is started.
Let engine idles for approximately for five minutes.
6
Adjust frequency with the Frequency Adjust Screw.
7
Rated frequency
50Hz(1500min
60Hz(1800min
Adjust the voltage regulator dial to the specified voltage.
8
50Hz Operation
60Hz Operation
* The values in brackets are for when set to 200/220V.
Turn on the Circuit Breaker to activate power supply.
9
No-load frequency
-1
)
52.5Hz(1575min
-1
)
63.0Hz(1890min
400V [200V]