Fastpak™ "Settings Group" Menu Record; Operator Settings Group - Trane CVHE Information Manual

Clear language display
Table of Contents

Advertisement

FastPak™ "Settings Group" Menu Record

Operator Settings Group:

Menu item
1
Purge Operating Mode
2
Front Panel Chilled Wtr Setpt
3
Front Panel Current Limit Setpt
4
Chilled Water Reset Type
5
Reset Ratio
6
Start Reset Setpoint
7
Max Reset Setpoint
8
Ice Building
Panel Ice Termination Setpoint (Displayed if
Ice Building Enabled)
9
10
Ice to Normal Cooling Timer (Displayed only
if Ice Building Option" is installed)
11
Chilled Water Setpoint Source
12
Current Limit Setpoint Source
13
Ice Termination Setpoint Source (Displayed
only if "Ice Building Option" is installed)
14
Setpoint Source Override
Information Manual
Choices
Stop, On, Auto, Adaptive
Auto
0-65 Deg F, -17.8-18.3
44.0
Deg C
40 to 100%
100%
Return, Constant Return,
Disable
Disable
10 to 120%
50%
°
°
4 to 30
F, 2.2 to 16.7
C
10
°
°
0 to 20
F, 0.0 to 11.1
C
5
Disable, Enable
Disable
°
°
20 to 32
F, -6.7 to 0
C
27
0 to 10 mm.
5 minutes
Front Panel, External
Front Panel
SourceFuture 1, Future 2
Front Panel, External
Front Panel
Source, Future 1, Future 2
Front Panel, Future 1,
Front Panel
Future 2, Future 3
None, Use Front Panel
None
Setpoints, Override
Tracer-Use Default
Setpoints (available only if
Tracer Option is installed)
Default
Design/Actual
°
F, 6.7 C
°
°
F, 5.6
C
°
°
F, 2.8
C
°
°
F, -2.8
C