under Duplex Control and it is Compressor B.

Reset Ratio

This is the aggressive value. A higher number is a
quicker response.
[type] Reset Ratio:
Press (+)(-) to Change Setting
The values for Reset Ratio for each of the reset types
are:
Reset
Increment
Reset
Ratio
Type
Range
Return
10 to
120%
Outdoor
80 to -80%

Start Reset Setpoint

This is the Delta T the unit is trying to maintain.
[type] Start Reset Setpoint: xxx.x F
Press (+)(-) to Change Setting
The values for Start Reset for each of the reset types
are:
Start
Increment
Reset
Reset
Type
Range
°
Return
4 to 30
F
(2.2 to
°
16.7
C)
Outdoor
50 to
°
130
F (10
°
to 54.4
C)

Maximum Reset Setpoint

Controllable Maximum Reset value. Allows a reset
"Up" of this value. The chilled water is maintained
between the leaving chilled water setpoint and the
new reset value.
[type] Max Reset Setpoint: xxx.x F
Information Manual
xxx %
(Eng.
Increment
Default
units)
(SI)
Value
1%
1%
50%
1%
1%
10%
(Eng.
Increment
Default
units)
(SI)
Value
°
°
1
F
1
C
10
(5.6
°
°
1
F
1
C
90
(32.2
Press (+)(-) to Change Setting
The values for Maximum Reset for each of the reset
types are:
Maximum
Reset
Type
Return
0 to 20
Outdoor
0 to 20

Ice Building Enable

The following will be displayed only if the ice building
option is installed.
Ice Building:
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory
Default) and Enable.

Front Panel Ice Termination Setpoint

The following will be displayed only if ice building
option is installed.
Panel Ice Termination Setpoint:xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 20.0 to 32.0
°
F
increments of 1 or 0.1
°
C)
Service Setup Screen xxx or xxx.x. Factory Default is
°
°
27.0
F (-2.8
°
F
°
C)
Ice Making To Normal Cooling Transition
Timer
The following will be displayed only if the ice building
option is installed. This allows for a timed idle/stop
period for (X) minutes when coming out of ice before
going into the cooling mode (timed by Chiller).
Ice-To-Normal Cooling Timer: xx min
Press (+)(-) to Change Setting
Increment
Reset
(Eng.
Increment
Range
units)
°
°
F
1
F
1
(0.1 to
°
11.1
C)
°
°
F
1
F
1
(0.1 to
°
11.1
C)
°
F (-6.7 to 0.0
°
°
F or
C depending on the
C).
Operator Settings
Default
(SI)
Value
°
°
C
5
F
°
(2.8
C)
°
°
C
5
F
°
(2.8
C)
[d/e]
°
C) in
23