Programmable Relay Outputs; Current Transducer Setpoint; Current Transducer At 100% Rla; Compressor Power Source - Trane CVHE Information Manual

Clear language display
Table of Contents

Advertisement

Factory Default is % RLA.

Programmable Relay Outputs

The following represents three menu items and is
repeated for [N] = 1, 2, or 3.
Program Relay [N]: [Relay]
Press <+> <-> To Change Setting
Possible values of [Relay] are:
Not Used
Comp Running
MMR Alarm
MAR Alarm
MMR + MAR Alarm
Factory Default for
[N] = 1 is MMR + MAR Alarm.
[N] = 2 is Comp Running.
[N] = 3 is Not Used.

Current Transducer Setpoint

The following will only be displayed if starter type is
set to "Stand Alone - No Starter Module".
Current Xducer: [Setting]
Press <+> <-> To Change Setting
Possible values for [Setting] are: Cutler Hammer;
Other Factory Default is "Cutler Hammer"
Note: Select "Cutler Hammer" if starter has an A-1
module, otherwise select "Other".
Information Manual
Limit Warning
Ice Making
Head Relief Request
Tracer Controlled
Max Capacity

Current Transducer at 100% RLA

The following will only be displayed if Current
Transducer is set to "Other".
Current Xducer at 100% RLA: XX.X VDC
Press <+> <-> To Change Setting
Range of values is -10.0 to -5.0 VDC in increments of
0.1 VDC
Note: Calculate setpoint as follows:
Current Transducer at 100% RLA =
Machine LRA
------------------------------------- - X 10
CT Span

Compressor Power Source

Cprsr Power Source: [status]
Press (+)(-) to Change Setting
Possible settings for [status] are: Utility (Factory
Default) and Engine/Generator.
Machine Configuration
– (
)
49