Trane Tracer AdaptiView User Manual
Trane Tracer AdaptiView User Manual

Trane Tracer AdaptiView User Manual

Display for centravac water-cooled chillers
Hide thumbs Also See for Tracer AdaptiView:
Table of Contents

Advertisement

User Guide
Tracer® AdaptiView™ Display for
CenTraVac™ Water-cooled Chillers
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.
March 2020
SAFETY WARNING
CTV-SVU01G-EN
X39641071060

Advertisement

Table of Contents
loading

Summary of Contents for Trane Tracer AdaptiView

  • Page 1 User Guide Tracer® AdaptiView™ Display for CenTraVac™ Water-cooled Chillers X39641071060 SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
  • Page 2 Warnings, Cautions, and Notices Safety advisories appear throughout this manual as required.Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions. The three types of advisories are defined as follows: Indicates a potentially hazardous situation which, if not avoided, could result in WARNING death or serious injury.
  • Page 3 N N o o n n - - T T r r a a n n e e p p e e r r s s o o n n n n e e l l s s h h o o u u l l d d a a l l w w a a y y s s f f o o l l l l o o w w l l o o c c a a l l r r e e g g u u l l a a t t i i o o n n s s . . Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
  • Page 4: Table Of Contents

    Table of Contents Product Overview............. . 7 Equipment Description .
  • Page 5 T T a a b b l l e e o o f f C C o o n n t t e e n n t t s s Creating a Custom Data Graph With No Previously Defined Data Graph Points .
  • Page 6 T T a a b b l l e e o o f f C C o o n n t t e e n n t t s s Reports ..............65 Log Sheet .
  • Page 7: Product Overview

    11 inches. Five pivot points enable full articulation as described in the following specifications and in the figure: Figure 1. The Tracer AdaptiView mounting arm • Two horizontal pivots points 90º right or left (180º total) •...
  • Page 8: Touchscreen Guidelines

    CenTraVac Chillers with Tracer AdaptiView Control) • PRGF-SVX001*-EN (Installation, Operation, and Maintenance: EarthWise Purge System with Tracer AdaptiView Control for Water-cooled CenTraVac Chillers with R-123 Refrigerant) • PRGG-SVX001*-EN (Installation, Operation, and Maintenance: Purge System with Tracer AdaptiView Control for Water-cooled CenTraVac Chillers with R-514A Refrigerant) •...
  • Page 9: Chiller Status Area

    P P r r o o d d u u c c t t O O v v e e r r v v i i e e w w Figure 2. Tracer AdaptiView display (Home screen for Simplex chillers is shown) “Chiller Status Area,”...
  • Page 10: Main Display Area/Home Screen

    P P r r o o d d u u c c t t O O v v e e r r v v i i e e w w Table 1. Chiller status area (continued) Button/Touch target Description The water temperature touch target shows one of the following, depending on whether the chiller is in heating or cooling mode (also referred to as the Active Control Type): Water temperature touch target •...
  • Page 11 P P r r o o d d u u c c t t O O v v e e r r v v i i e e w w Table 2. Home screen touch targets and buttons Touch target Description Compressor for Simplex chillers This compressor touch target chiller provides information on:...
  • Page 12 P P r r o o d d u u c c t t O O v v e e r r v v i i e e w w Table 2. Home screen touch targets and buttons (continued) Touch target Description Motor for Duplex chillers The motor touch target provides information on:...
  • Page 13 P P r r o o d d u u c c t t O O v v e e r r v v i i e e w w One of the following graphics will appear on the display for Duplex™ chillers: •...
  • Page 14: Main Display Area/Screen Saver

    P P r r o o d d u u c c t t O O v v e e r r v v i i e e w w Main Display Area/Screen Saver After 30 minutes of inactivity, the screen dims and a screen saver appears in the main display area as shown in the following figure.
  • Page 15 P P r r o o d d u u c c t t O O v v e e r r v v i i e e w w Figure 4. Component screen example for Simplex chillers 1. Data Graph shortcut button 2.
  • Page 16 P P r r o o d d u u c c t t O O v v e e r r v v i i e e w w Figure 5. Component screen example for Duplex chillers Data Graph shortcut button 2.
  • Page 17: Main Menu Area

    P P r r o o d d u u c c t t O O v v e e r r v v i i e e w w Main Menu Area The main menu area (shown in “Screen Overview,” p. 8) always remains visible at the bottom of the display.
  • Page 18: Stopping/Restarting Chiller Operation

    Stopping/Restarting Chiller Operation You can start or stop the chiller from the Tracer® AdaptiView™ display by using the Auto and Stop buttons. The buttons are located in upper right. Stopping the Chiller You can stop the chiller in two ways: •...
  • Page 19: Restarting The Chiller

    S S t t o o p p p p i i n n g g / / R R e e s s t t a a r r t t i i n n g g C C h h i i l l l l e e r r O O p p e e r r a a t t i i o o n n Figure 7.
  • Page 20: Alarms

    Alarms You can use the Tracer® AdaptiView™ display to view alarms and to reset them. Alarms are communicated to the display immediately upon detection. The Alarms Screen Touch the A A l l a a r r m m s s button in the main menu area at the bottom of the screen to view the Alarms screen.
  • Page 21: Alarm Icons

    A A l l a a r r m m s s Alarm Icons Alarm icons, which appear in the left-most column of the alarms screen and on the alarms indicator button if there is an existing alarm, are distinguished by their shape and color. Their meaning is explained in the following table.
  • Page 22: Resetting Alarms

    A A l l a a r r m m s s Resetting Alarms Some alarms require reset to move from the active to the historic state, even if the issue causing the alarm has been resolved. These manual reset alarms are sometimes referred to as latching alarms.
  • Page 23: Reports

    On the Reports screen, touch L L o o g g S S h h e e e e t t to view the information that is itemized in “Log Sheet,” p. 65 for Simplex chillers, and in “Log Sheet,” p. 79 for Duplex™ chillers. The items included in the Log Sheet are those recommended by Trane. Refer to current Trane service literature for more information. CTV-SVU01G-EN...
  • Page 24: Viewing The Ashrae Chiller Log

    R R e e p p o o r r t t s s Viewing the ASHRAE Chiller Log On the Reports screen, touch A A S S H H R R A A E E C C h h i i l l l l e e r r L L o o g g to view the information that is itemized in “ASHRAE Chiller Log,”...
  • Page 25: Editing A Custom Report

    R R e e p p o o r r t t s s N N o o t t e e : : A page number appears in the lower right corner of the screen. If a screen contains more than one page, up/down arrows also appear for viewing the other pages, as in the following figure.
  • Page 26: About This Chiller

    R R e e p p o o r r t t s s About this Chiller On the Reports screen, touch A A b b o o u u t t T T h h i i s s C C h h i i l l l l e e r r to view the following unit information: •...
  • Page 27 R R e e p p o o r r t t s s Submodes are dependent on the top-level mode. Their appearance on the Chiller Operating Modes screen has the following characteristics: • The newest submode appears at the top of the submode list. •...
  • Page 28: Duplex Chillers

    R R e e p p o o r r t t s s Table 5. Chiller top-level operating modes and corresponding submodes for Simplex chillers (continued) Top-level mode Description Corresponding submodes Current Limit Phase Unbalance Limit Condenser Pressure Limit Evaporator Temperature Limit Running—Limit Compressor is running with limits in effect.
  • Page 29 R R e e p p o o r r t t s s For Duplex™ chillers, the Chiller Operating Modes screen shows top-level modes and submodes for the chiller (Table 6, p. 29) and for the circuits (Table 7, p. 30).
  • Page 30 R R e e p p o o r r t t s s Table 6. Chiller top-level operating modes and corresponding submodes for Duplex chillers (continued) Top-level mode Description Corresponding submodes Evaporator Pump Off Delay (MIN:SEC) Condenser Pump Off Delay (MIN:SEC) The chiller is still running, but shutdown is imminent.
  • Page 31: Purge Operating Modes

    If less than six submodes are active, the submode rows that do not apply are blank. For detailed information about purge operating modes and submodes, refer to PRGF-SVX001*- EN (Installation, Operation, and Maintenance: EarthWise Purge System with Tracer AdaptiView Control for Water-cooled CenTraVac Chillers with R-123 Refrigerant) or PRGG-SVX001*-EN (Installation, Operation, and Maintenance: Purge System with Tracer AdaptiView Control for Water-cooled CenTraVac Chillers with R-514A Refrigerant), as appropriate.
  • Page 32: Data Graphs

    Data Graphs You can use the Tracer® AdaptiView™ display to view a variety of default data graphs and to create up to six custom data graphs with up to eight data points per graph. The data sample rate is 30 seconds, and the data storage duration is 48 hours. These rates cannot be adjusted. The Data Graphs Screen Touch the D D a a t t a a G G r r a a p p h h s s button in the main menu area to view the Data Graphs screen shown in the following figure.
  • Page 33: Viewing Data Graphs

    D D a a t t a a G G r r a a p p h h s s • Chiller Overview 2 • Evaporator • Condenser C C i i r r c c u u i i t t 1 1 •...
  • Page 34: Changing The Scales On Data Graphs

    D D a a t t a a G G r r a a p p h h s s Changing the Scales on Data Graphs C C h h a a n n g g i i n n g g t t h h e e S S c c a a l l e e o o f f t t h h e e X X - - a a x x i i s s The X-axis scale defaults to the most recent 60 minutes with 15 minutes in between the time labels that appear across the bottom of the graph.
  • Page 35: Creating Custom Data Graphs

    D D a a t t a a G G r r a a p p h h s s screen. 4. Touch the appropriate numbers to change the current value. The new value appears above the keypad. 5. Touch the E E n n t t e e r r button. The graph you were previously viewing appears with changed maximum and/or minimum values.
  • Page 36 D D a a t t a a G G r r a a p p h h s s CenTraVac Duplex Chillers ,” p. 77). Figure 18. Add/Remove screen example 4. To choose points to include in the custom data graph, you can do any of the following: •...
  • Page 37: Points

    D D a a t t a a G G r r a a p p h h s s Figure 19. Custom data graph example Creating a Custom Data Graph With No Previously Defined Data Graph Points 1. Touch the C C r r e e a a t t e e C C u u s s t t o o m m button at the top left of the Data Graphs screen (Figure 14, p.
  • Page 38: Deleting A Custom Data Graph

    D D a a t t a a G G r r a a p p h h s s Figure 20. Edit Data Point screen Deleting a Custom Data Graph Touch the D D e e l l e e t t e e button at the top of a custom graph screen to delete the custom graph. CTV-SVU01G-EN...
  • Page 39: Equipment Settings

    Equipment Settings You can use the Tracer® AdaptiView™ display to monitor and change a variety of equipment settings. The Settings Screen Touch the S S e e t t t t i i n n g g s s button in the main menu area (see “Main Menu Area,”...
  • Page 40 E E q q u u i i p p m m e e n n t t S S e e t t t t i i n n g g s s Figure 22. Example equipment settings screen (Chiller Settings shown) To change an equipment setting, follow this procedure: 1.
  • Page 41 E E q q u u i i p p m m e e n n t t S S e e t t t t i i n n g g s s Figure 23. Example equipment settings screen with buttons for changing setting •...
  • Page 42: Chiller Settings

    E E q q u u i i p p m m e e n n t t S S e e t t t t i i n n g g s s – When you enter a new number, the value in the N N e e w w v v a a l l u u e e field is deleted and replaced with the new entry.
  • Page 43: Service Settings

    Some setpoints can be controlled from more than one source; these are referred to as arbitrated setpoints. Arbitrated setpoints can be: • Communicated from a building automation system (BAS)—Refers to a Trane or other BAS that can communicate with chiller controls over a network. •...
  • Page 44: Changing The Setpoint Source

    E E q q u u i i p p m m e e n n t t S S e e t t t t i i n n g g s s Table 10. Setpoint source choices and corresponding arbitration (continued) Priority BAS/Ext/FP Ext/FP...
  • Page 45: From An Arbitrated Setpoint Screen

    E E q q u u i i p p m m e e n n t t S S e e t t t t i i n n g g s s 2. From the Settings screen, touch the C C h h i i l l l l e e r r S S e e t t t t i i n n g g s s button. The Chiller Settings screen appears.
  • Page 46: Feature Settings

    E E q q u u i i p p m m e e n n t t S S e e t t t t i i n n g g s s Feature Settings The following table lists the settings that are available as buttons on the Feature Settings menu screen, along with their corresponding setting options.
  • Page 47: Purge Settings

    E E q q u u i i p p m m e e n n t t S S e e t t t t i i n n g g s s Purge Settings The following table lists the settings that are available as buttons on the Purge Settings menu screen, along with their corresponding setting options.
  • Page 48 E E q q u u i i p p m m e e n n t t S S e e t t t t i i n n g g s s Table 14. Manual Control settings menu screen: Buttons, available setting options, and status points (continued) Available setting Current Status points...
  • Page 49: Changing A Manual Control Setting

    E E q q u u i i p p m m e e n n t t S S e e t t t t i i n n g g s s Changing a Manual Control Setting To change a manual control setting, follow this procedure: 1.
  • Page 50 E E q q u u i i p p m m e e n n t t S S e e t t t t i i n n g g s s Figure 28. Manual Control Settings screen (Evaporator Pump Override shown) CTV-SVU01G-EN...
  • Page 51: Display Settings

    Display Settings You can use the Tracer® AdaptiView™ display to change the format of the information that appears on the display, and to clean the touch screen. Settings Screen Touch the S S e e t t t t i i n n g g s s button in the main menu area (refer to “Screen Overview,”...
  • Page 52 D D i i s s p p l l a a y y S S e e t t t t i i n n g g s s Figure 30. Display Preferences screen Each of the buttons in the previous figure shows the name of a display preference and its format (current value).
  • Page 53 D D i i s s p p l l a a y y S S e e t t t t i i n n g g s s Figure 31. Example of a display preference screen To change the format: 1.
  • Page 54: Viewing And Changing The Language Preference

    D D i i s s p p l l a a y y S S e e t t t t i i n n g g s s D D i i s s p p l l a a y y U U n n i i t t s s Use the Display Units screen to choose from the following display units: •...
  • Page 55 D D i i s s p p l l a a y y S S e e t t t t i i n n g g s s Figure 32. Language screen The language that is currently in use on the display is expressed as the current value on the Language screen.
  • Page 56: Viewing And Changing Date And Time Preferences

    D D i i s s p p l l a a y y S S e e t t t t i i n n g g s s Viewing and Changing Date and Time Preferences On the Settings screen, touch D D a a t t e e a a n n d d T T i i m m e e to view the Date and Time screen, shown in the following figure.
  • Page 57: Clean Touchscreen

    D D i i s s p p l l a a y y S S e e t t t t i i n n g g s s Clean Touchscreen On the Settings screen, touch C C l l e e a a n n T T o o u u c c h h s s c c r r e e e e n n to disable the Tracer® AdaptiView™ display screen for 15 seconds so that you can clean the screen without it responding to touch.
  • Page 58: Security Settings

    Security Settings If security if enabled, the Tracer® AdaptiView™ display requires that you log in with a four-digit security PIN to make setting changes that are protected by security. This feature prevents unauthorized personnel from doing so. There are two levels of security, each allowing specific changes to be made.
  • Page 59: Enabling Security

    S S e e c c u u r r i i t t y y S S e e t t t t i i n n g g s s Figure 36. Security screen 2. Touch the D D i i s s a a b b l l e e button. The button becomes shaded. 3.
  • Page 60 S S e e c c u u r r i i t t y y S S e e t t t t i i n n g g s s Figure 37. Log In screen 2. Use the keypad to enter your PIN. •...
  • Page 61: Logging Out

    S S e e c c u u r r i i t t y y S S e e t t t t i i n n g g s s Logging Out To log out: 1. Touch the L L o o g g O O u u t t button. A confirmation screen appears as shown in the following figure. Figure 38.
  • Page 62: Troubleshooting

    Troubleshooting The following table contains information to help troubleshoot the Tracer® AdaptiView™ displays. Table 15. Common error messages with possible causes and solutions Issue Possible Causes/Solutions The screen only partially displays; the Auto and Stop buttons The UC800 configuration is invalid. appear, but there is no text.
  • Page 63: Appendix A: Data For Centravac Simplex Chillers

    Appendix A: Data for CenTraVac Simplex Chillers The following lists contain all of the data available for viewing on a Tracer® AdaptiView™ display that is connected to a CenTraVac™ Simplex chiller. Component Screen Data Chiller configuration determines which of the following settings and status points appear on the display.
  • Page 64 A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 18.
  • Page 65: Reports

    A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 20.
  • Page 66 A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 23.
  • Page 67: Ashrae Chiller Log

    A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 25.
  • Page 68 A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 26.
  • Page 69: Items Available To Include In Custom Reports

    A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 26.
  • Page 70 A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 28.
  • Page 71 A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 30.
  • Page 72: Data Graph Data Points

    A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 32.
  • Page 73 A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 35.
  • Page 74 A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 39.
  • Page 75: Data Points In Custom Data Graphs

    A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Data Points in Custom Data Graphs Table 44.
  • Page 76 A A p p p p e e n n d d i i x x A A : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c S S i i m m p p l l e e x x C C h h i i l l l l e e r r s s Table 47.
  • Page 77: Appendix B: Data For Centravac Duplex Chillers

    Appendix B: Data for CenTraVac Duplex Chillers The following lists contain all of the data available for viewing on a Tracer® AdaptiView™ display that is connected to a CenTraVac™ Duplex™ chiller. Component Screen Data Chiller configuration determines which of the following settings and status points appear on the display.
  • Page 78: Reports

    A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Table 52.
  • Page 79: Log Sheet

    A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Log Sheet Table 54.
  • Page 80: Ashrae Chiller Log

    A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Table 56.
  • Page 81 A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Table 58.
  • Page 82: Items Available To Include In Custom Reports

    A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Items Available to Include in Custom Reports Table 59.
  • Page 83: Data Graph Data Points

    A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Table 63.
  • Page 84 A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Table 65.
  • Page 85 A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Table 70.
  • Page 86: Data Points In Custom Data Graphs

    A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Table 74.
  • Page 87 A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Table 77.
  • Page 88 A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Table 78.
  • Page 89 A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Table 79.
  • Page 90 A A p p p p e e n n d d i i x x B B : : D D a a t t a a f f o o r r C C e e n n T T r r a a V V a a c c D D u u p p l l e e x x C C h h i i l l l l e e r r s s Table 79.
  • Page 91 N N o o t t e e s s CTV-SVU01G-EN...
  • Page 92 For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.