Field Start-up
Field Start-up
Important! FACTORY DEFAULT SETTINGS: Menu
items that are programmable using the keypad may
have a selectable choice that is listed as Factory
Default. This Factory Default setting is the software
default that is initially factory-programmed for a new
module assembly and may NOT be the correct
setting for a specific operating chiller. Always review
all settings when any module is replaced to verify
that the settings agree with the desired settings that
were selected at initial startup or programmed at the
factory.

Field Startup

The Field Startup Group password is + + - - + +
<Enter>. The Field Startup Group contains items that
are primarily associated with Field Commissioning of
the chiller as well as the fundamental control and
protection of the chiller subsystems. If the field
startup password is entered, the display goes to the
menu defined below. If a key is not pressed every 10
minutes in this password protected menu, the display
returns to the Chiller Operating Mode display of the
Chiller Report, and the password must be entered
again to return to this menu.

Field Start-up Group Heading

Field Start-up Group Settings
Press (Next)(Previous) To Continue
This header appears when the headers do not
appear in the Service Settings menu.

Keypad/Display Lock Feature Enable

This feature permits the entire Keypad and Display to
be locked out. A message appears on the screen to
describe this condition. No access is permitted to
either the Report screens or the Setting Screens
when this feature is both Enabled here and Locked at
the Service Settings Menu. It is important to note that
30
in this condition, both the <Stop> and <Auto> keys
do not function.
Keypad/Display Lock Feature: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory
Default) and Enable.
When the keypad lock feature is Disabled, the
keypad lock display does not appear in the non-
password protected area of the Service Settings
menu and the Keypad/Display cannot be locked.
When the keypad/display lock feature is Enabled, the
keypad lock display does appear in the Service
Settings menu so the keypad can be locked.

Menu Settings Password Enable

The Menu Settings Password permits the Settings in
each of the menus to be password protected. All
Report Menus and Setting Menus can still be viewed
at any time if this feature is either Enabled or
Disabled; the <Stop> and <Auto> keys also remain
active. If this feature is Enabled, then all Menu
Settings are password protected.
Menu Settings Password Feature: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory
Default) and Enable.
When the feature is Disabled, the Menu Setting
Password display does not appear at the top of each
of the Settings Menus and the Menu Settings cannot
be password protected. When the Menu Setting
Password feature is Enabled, the Menu Settings
Password display appears just below each of the
Settings Menu Headers so the settings can be
changed if the proper password is entered.