Evaporator Entering and Leaving Water
Temperatures
Evap Entering Water Temp: xxx.x f/c
Evap Leaving Water Temp: xxx.x f/c

Cond Entering and Leaving Water Temps

Dashes will be displayed for condenser entering or
leaving water temperature if the corresponding input
is open or shorted.
Cond Entering Water Temp: xxx.x f/c
Cond Leaving Water Temp: xxx.x f/c

Active Current Limit Setpoint

Active Current Limit Setpoint: xxx %
Press (Next)(Previous) To Continue
Active Current Limit Setpoint/Current
Limit Setpoint Source
Active Current Limit Setpoint: xxx %
[settings source] CLS:
Settings source will be one of the following: Front
Panel, Tracer, External Source, or Ice Building.
Evaporator Water Flow/ Condenser
Water Flow
The following will be displayed only if the Differential
Water Sensing Option is installed.
Approx Evaporator Water Flow:xxx.x gpm/lpm
Approx Condenser Water Flow: xxx.x gpm/lpm
The possible values for units are "gpm" or "lpm."
Information Manual

Chiller Tons

The following will be displayed only if the Differential
Water Sensing Option is installed.
Approximate Chiller Capacity: xxxx Tons/KW
Press (Next)(Previous) To Continue
The possible values for units are "Tons" or "KW."

Outdoor Temperature

If the outdoor air temperature input is open or
shorted and neither Outdoor Air Reset nor Low
Ambient Lockout is enabled, display "------" in place
of "xxx.x F." Otherwise the temperature received
from the chiller module is displayed.
Outdoor Air Temperature: xxx.x f/c
Press (Next)(Previous) To Continue

Aux. Bundle or Heat Recovery Temps

The following will be displayed only if either the Heat
Recovery Option or Aux Condenser Option is
installed.
Aux/Heat Rcvy Ent Wtr Temp: xxx.x f/c
xxx %
Aux/Heat Rcvy Lvg Wtr Temp: xxx.x f/c

Chilled Water Setpoint Source

Chld Wtr Setpt Source: [settings source]
Reset Condition: [reset condition]
Settings source will be one of the following: Front
Panel, Tracer, or External Source.
Reset condition will be one of the following: None,
Outdoor Temp, or Return Wtr Temp.
Chiller Report