Refrigerant Report

Report Heading

Refrigerant Temp & Pressure Report
Press (Next)(Previous) To Continue
Evaporator and Condenser Refrigerant
Pressure
Evap Rfgt Pressure: xxx.x psig
Cond Rfgt Pressure: xxx.x psig
Saturated Evap Temperature/Evap
Refrigerant Pressure
Saturated Evap Temp: xxx.x f/c
Evap Rfgt Pressure: xxx.x psig
Saturated Cond Temperature/Cond
Refrigerant Press
Saturated Cond Temp: xxx.x f/c
Cond Rfgt Pressure: xxx.x psig
Saturated Evap Temp. and Discharge
Temp.
The Discharge Temp will be displayed only if the
Discharge Sensor Option is installed.
Saturated Evap Rfgt Temp: xxx.x f/c
Compressor Discharge Temp: xxx.x f/c
Information Manual

Purge Operating Mode/Purge Status

The following screen(s) does not appear if the
selected Purge Control/Type is "Stand-Alone Purge."
Purge Operating Mode:
Purge Status:
Possible values of [Mode] are: Auto, Stop, On, or
Adaptive.
Possible values of [Status] are:
Idle
Running
Pumpout
Service Pumpout
Running - Pumpout inhibited by
low temp.
Pumpout Maximum Rate
Disabled

Purge Alarm Message

The following screen(s) is not displayed if the
selected Purge Control/Type is "Stand-Alone Purge."
Purge Alarm Msg: [Status]
[Help Message]
Possible values for [Status] are: No Diagnostics
Present (the [Help Message] is: Press (Next)
(Previous) To Continue) or Diagnostic Alarm (the
[Help Message] is: Go to Diag. Menu for Description/
Reset).
Refrigerant Report
[Mode]
[Status]
(Condensing Unit is Off)
(Condensing Unit is On)
(Temperature Initiated
pumpout)
(Pumpout initiated by service
switch)
(Pumpout inhibited by low
liquid temp)
(Max. pumpout rate alarm
disabled)
15