Table 1
Operating Modes
Unit Operation
Local Stop: Cannot Be Overridden By
Remote Display Stop: Chiller May Be
Set To Auto By Any Ext Or Rmt Device
Stop
Auto
Waiting For Tracer Communications
Starting Is Inhibited By Staggered Start
Time Remaining:
Inhibit Timer: Time Remaining MIN:SEC
Prelubrication Time:
Prelubrication Time:
Initialize
Start
Run
Information Manual
Operating Mode Display*
(First Line/Second Line)
Resetting
Any External Or Remote Device
Remote Run Inhibit
From External Source
Remote Run Inhibit
From Tracer
Heat Sink Temp Start Inhibit
Diagnostic Shutdown Stop
Diagnostic Shutdown Auto
Auto
Waiting For Evaporator Water Flow
Auto
Waiting For A Need To Cool
To Establish Operating Status
MIN:SEC
Starting Is Inhibited By Restart
Establishing Cond Water Flow
Establishing Oil Pressure
Establishing Cond Water Flow
MIN:SEC
Cond Water Is Flowing
MIN:SEC
Cond Water Is Flowing
Establishing Oil Pressure
Cond Water Is Flowing
Performing IGV BPI Search and
Calibration
Cond Water Is Flowing
PreStart Unload Time Remaining:
MIN:SEC
Starting Compressor
Unit Is Running
Unit Is Running
Capacity Limited By High Current
Operating Mode Display*
Unit Operation
(First Line/Second Line)
Capacity Limited By Phase Unbalance
Capacity Limited By High Cond Press
Capacity Limited By Low Evap Temp
Capacity Limited By Vane Open Travel
Run
Minimum Capacity Due To Vane Closed
Unit Is Running in Surge Condition
Unit Is Running; Capacity Limited By
Pulldown Rate Based Soft Loading
Unit Is Running; Capacity Limited By
Current Based Soft Loading
Auto
Waiting For Condenser Water Flow
Establishing Evap Water Flow
Establishing Oil Pressure
Establishing Evap Water Flow
Prelubrication Time:
Prelubrication Time:
Performing IGV BPI Search & Calibration
Establishing Evap Water Flow
Performing IGV BPI Search & Calibration
Unit is Running; Base Loaded
Unit is Running; Base Loaded
Run
Capacity Limited By High Current
Unit is Running; Base Loaded
Capacity Limited By Phase Unbalance
Unit Is Running; Base Loaded
Capacity Limited By High Cond Press
Unit Is Running; Base Loaded
Capacity Limited By Low Evap Temp
Unit is Running; Base Loaded
At Vane Open Travel Stop
Unit is Running; Base Loaded
At Vane Closed Travel Stop
Unit is Running; Base Loaded
ASHRAE Guideline 3 Report
Unit Is Running
Unit Is Running
Unit Is Running
Unit is Running
Stop
Unit Is Running
Travel Stop
Auto
MIN:SEC
Evap Water Is Flowing
MIN:SEC
Evap Water Is Flowing
In Surge Condition
5