5-2. Switches

Power Switch / Air Bleeding
(1)
(2) Emergency Stop Button
(3) Main Circuit Breaker
< Note >
 Do not use RCCB as the ON/OFF switch to the load.
(4) 3-Phase Circuit Breaker
1-Phase Circuit Breaker
3P Breaker
< Note >
 Do not use this breaker as the ON/OFF switch to the load.
This is the main Power Switch of the generator.
When the Power Switch turned to OFF position, the Controller is OFF.
When the Power Switch turned to AIR BLEEDING position,
automatically starts air-bleeding device.
This button is used to stop the engine in emergency.
By inserting the button, the engine stops.
Be sure to restore the Power Switch to OFF and re-set
the button, turning clockwise after using the emergency stop button.
By turning this circuit breaker on the control panel to ON,
Power will be transferred to the output receptacles and to the
load side.
The breaker trips to OFF, either overload or short-circuit.
Each receptacle, 3-Phase and 1-Phase is
incorporated with circuit breaker respectively.
The breaker trips on overload or short-circuit on
to stop power transmission to load.
1P Breaker
11