7 Technical data

7 Technical data
7.1 Temperature
Ambient temperature:
Storage temperature:
7.2 Product compliance
EMC Directive:
Explosion protection:
ATEX marking:
IECEx marking:
NEC marking:
EAC marking:
Approvals:
SIL:
GEMÜ 1242
0 — 60 °C
-10 — 70 °C
2014/30/EU
Technical standards used:
ATEX (2014/34/EU) and IECEx, order code Special version X
NEC 500 (ISA 12.12.01), order code Special version Y
EAC according to TR CU 012/211 - ATEX
Gas:
II 3G Ex ec nC IIC T4 Gc X
Dust:
II 3D Ex tc IIIC T 80 °C Dc X
Gas:
Ex ec nC IIC T4 Gc
Dust:
Ex tc IIIC T80°C Dc
Certificate: IECEx IBE 18.0029 X
Class I, Division II, Groups C & D, T4
2Ex e nC IIC T4 Gc X
Certificate: ЕАЭС RU C-DE.BH02.B.00231/19
Fieldbus/
-
communication
Product description:
Device type:
Valid software version:
Safety function:
HFT (Hardware Fault Tolerance):
MTTR (Mean Time To Restoration):
MTBF (Mean Time Between Failures):
Further information, see SIL safety manual
24 V
AS-Interface
Travel sensor ver-
sion 050: AS-Inter-
face certificate
no. 96001
Travel sensor ver-
sion 075: AS-Inter-
face certificate
no. 125601
GEMÜ electrical position indicator 1242
B
V1.1.X.X
The fail-safe state is defined as a High (24 V DC) signal
at pin 4 (device version 24 V IO-Link), if the current posi-
tion of the integrated travel sensor is smaller than the
switch point CLOSED (default setting 12%).
0
24 hours
232 years
10 / 41
IO-Link
DeviceNet
Travel sensor ver-
n.n.
sion 050: IO-Link
specification V
1.1
Travel sensor ver-
sion 075: IO-Link
specification V
1.1
www.gemu-group.com

Advertisement

Table of Contents
loading

Table of Contents