Maximum cable length
Baud rate [kBaud]
125
250
500

15.3 Inputs

Bit
Default
0, 1
not used
2
0
Programmingmode Operating mode
3
0
Position Closed
4
0
Position Open
5
0
Calibrationmode
6
0
Global warnings
7
0
Global errors
As seen from the DeviceNet master, Class 64h, Inst. 1h, Attr. 1h

15.4 Outputs

Bit
Default
0 ... 2 not used
3
0
Location function
4
not used
5
0
Manual program-
ming
6
0
Automatic program-
ming
7
not used
As seen from the DeviceNet master, Class 64h, Inst. 1h, Attr. 1h

15.5 Parameter overview

Class
Inst.
Attr.
Fh
1h
1h
Fh
2h
1h
www.gemu-group.com
Trunk cable
Thick cable
500 m
250 m
100 m
Designation
CLOSED position
OPEN position
Calibration mode
Warning
Error
Designation
Location function
Manual programming mode
Automatic programming mode:
Parameters
Inversion of LED colours
Inversion of signals
Thin cable
100 m
100 m
100 m
Function
Function
Length Data type Access Stand-
1 byte
Boolean Get/Set 0
1 byte
Boolean Get/Set 0
33 / 41
Drop cable
Max. cable length per
drop cable
6 m
6 m
6 m
0 = normal operation
1 = programming mode
0 = process valve not in CLOSED position
1 = process valve in CLOSED position
0 = process valve not in OPEN position
1 = process valve in OPEN position
0 = normal operation
1 = calibration mode
0 = warning not active
1 = warning active
0 = error not active
1 = error active
0 = location function not active
1 = location function active
0 = manual programming mode not act-
ive
1 = manual programming mode active
0 = automatic programming mode not
active
1 = automatic programming mode active
ard
value
0 = standard
1 = inversed
0 = standard
1 = inversed
15 Specific data - DeviceNet
Max. drop cable accu-
mulated length
156 m
78 m
39 m
Logic
Logic
Value range
GEMÜ 1242