7 Technical data

7 Technical data
7.1 Temperature
Ambient temperature:
Storage temperature:
7.2 Product compliance
EMC Directive:
Explosion protection:
ATEX marking:
IECEx marking:
7.3 Mechanical data
Installation position:
Weight:
Protection class:
Stroke:
Measuring range radial:
7.4 Electrical data
Electrical connection
type:
7.4.1 2-wire proximity switch
Switch type:
Supply voltage:
Current consumption:
Intrinsically safe charac-
teristic values:
GEMÜ 1241
0 — 60 °C
-10 — 70 °C
2014/30/EU
ATEX (2014/34/EU)
IECEx
Gas:
II 2G Ex ib IIB T4 Gb
Dust:
II 2D Ex ib IIIC T120°C Db
EC type examination certificate: IBExU21ATEX1097 X
Notified body: IBExU, No. 0637
Gas:
Ex ib IIB T4 Gb
Dust:
Ex IIIC T120°C Db
Certificate: IECEx IBE 21.0043 X
Optional
420 g
IP 67
5 — 75 mm
0° to 90°
M12 plug, 5-pin (code 01)
M16x1.5 Skintop cable gland for cable dia. 4.5 to 10 mm, recommended wire cross section
0.75 mm² x 8 cables (code 03)
2-wire, NAMUR, switch (code N1)
8 V DC
≤ 0.1 mA (damped)
≥ 3 mA (undamped)
Ui = 16 V
Ii = 52 mA
Pi = 169 mW
Li = 50 µH
Ci = 30 nF
8 / 20
www.gemu-group.com